Function Details SiME281501E31 Function and Control4.1.9 Automatic RestartPurposeThe purpose of the auto-restart function is to automatically resume the same operating mode as when theunit was operating when the power supply is restored after a power failure.Do not use the "Automatic Restart" function to daily start/stop the unit.Precautions when turning OFF power When you have to turn OFF the power supply in order to carry out maintenance, make sure to turn theremote control's ON/OFF switch OFF firstly. If you turn OFF the power supply while the remote control's ON/OFF switch is still ON, the "automaticrestart function" automatically starts the indoor unit fan immediately and the outdoor unit fan startsautomatically 3 minutes after the power supply is restarted. Do not start/stop the unit by disconnecting the power supply. Stop the unit by stop command from theremote controller or optional controller before disconnecting the power supply. Be sure that thecompressor and the outdoor unit fans are stopped before disconnecting the power supply so the"Refrigerant Recovery function" has been finished correctly. When restarting the unit after the power supply was disconnected for a longer period leave the unit OFFwith the power supply connected for about half an hour (Refer to "Crankcase Heater Control" &"Preheating Operation Control").4.1.10 Fan and Flap OperationsFan Flap RemoteControllerIndicationFCQHeatingOperation Hot Start from Defrost In Swing Operation OFF Horizontal SwingIn Airflow Direction Setting OFF Horizontal Set PositionDefrost In Swing Operation OFF Horizontal SwingIn Airflow Direction Setting OFF Horizontal Set PositionThermostat OFF In Swing Operation LL Horizontal SwingIn Airflow Direction Setting LL Horizontal Set PositionHot Start fromThermostat OFF (ColdAir Prevention)In Swing Operation LL Horizontal SwingIn Airflow Direction Setting LL Horizontal Set PositionStop (Error) In Swing Operation OFF Horizontal —In Airflow Direction Setting OFF Horizontal —Overload ThermostatOFF In Swing Operation LL Horizontal SwingIn Airflow Direction Setting LL Horizontal Set PositionCoolingOperation Thermostat ON inProgram Dry Mode In Swing Operation L Swing SwingIn Airflow Direction Setting L Set Position Set PositionThermostat OFF inProgram Dry Mode In Swing Operation OFF Swing SwingIn Airflow Direction Setting OFF Set Position Set PositionCooling Thermostat OFF In Swing Operation Setting Swing SwingIn Airflow Direction Setting Setting Set Position Set PositionStop (Error) In Swing Operation OFF Horizontal —In Airflow Direction Setting OFF Set Position —Freeze-up Prevention inProgram Dry Mode(Including CoolingOperation)In Swing Operation L Swing SwingIn Airflow Direction Setting L Set Position Set Position