4.2 Electrical Data - 380–500 VLine Power Supply 3 x 380–500 V AC (AutomationDrive FC 302), 3 x 380–480 V AC (AutomationDrive FC 301)PK 37 PK 55 PK75 P1K1 P1K5 P2K2 P3K0 P4K0 P5K5 P7K5AutomationDrive FC 301/AutomationDrive FC 302Typical Shaft Output [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5Enclosure IP20/IP21 A2 A2 A2 A2 A2 A2 A2 A2 A3 A3Enclosure IP20(AutomationDrive FC301 only)A1 A1 A1 A1 A1Enclosure IP55, 66 A5 A5 A5 A5 A5 A5 A5 A5 A5 A5Output currentHigh overload 160% for 1 minuteShaft output [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5Continuous(3 x 380–440 V) [A] 1.3 1.8 2.4 3 4.1 5.6 7.2 10 13 16Intermittent(3 x 380–440 V) [A] 2.1 2.9 3.8 4.8 6.6 9.0 11.5 16 20.8 25.6Continuous(3 x 441–500 V) [A] 1.2 1.6 2.1 2.7 3.4 4.8 6.3 8.2 11 14.5Intermittent(3 x 441–500 V) [A] 1.9 2.6 3.4 4.3 5.4 7.7 10.1 13.1 17.6 23.2Continuous kVA(400 V AC) [kVA] 0.9 1.3 1.7 2.1 2.8 3.9 5.0 6.9 9.0 11.0Continuous kVA(460 V AC) [kVA] 0.9 1.3 1.7 2.4 2.7 3.8 5.0 6.5 8.8 11.6Max. cable size(line power, motor, brake)[AWG] 2) [mm2]24 - 10 AWG0.00031–0.0062 in2 [0.2–4 mm2]24 - 10 AWG0.00031–0.0062 in2 [0.2–4mm2]Max. input currentContinuous(3 x 380–440 V) [A] 1.2 1.6 2.2 2.7 3.7 5.0 6.5 9.0 11.7 14.4Intermittent(3 x 380–440 V) [A] 1.9 2.6 3.5 4.3 5.9 8.0 10.4 14.4 18.7 23.0Continuous(3 x 441–500 V) [A] 1.0 1.4 1.9 2.7 3.1 4.3 5.7 7.4 9.9 13.0Intermittent(3 x 441–500 V) [A] 1.6 2.2 3.0 4.3 5.0 6.9 9.1 11.8 15.8 20.8Max. electrical fuses 1)[A] 10 10 10 10 10 20 20 20 32 32EnvironmentEstimated power lossat rated max. load [W] 4) 35 42 46 58 62 88 116 124 187 255Weight,enclosure IP20 4.7 4.7 4.8 4.8 4.9 4.9 4.9 4.9 6.6 6.6Enclosure IP55, 66 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 14.2 14.2Efficiency 4) 0.93 0.95 0.96 0.96 0.97 0.97 0.97 0.97 0.97 0.970.5–10 hp [0.37–7.5 kW] only available as 160% high overload.FC 300 Design Guide 4 AutomationDrive FC 300 SelectionMG.33.BC.22 - VLT® is a registered Danfoss trademark 4-34