VLT ® 5000 Series■ Introduction to Quick SetupThis Quick Setup will guide you through EMC correctinstallation of the frequency converter by connectingpower, motor and control wiring (fig. 1). Start/stopof motor is to be done with the switch.For VLT 5122 - 5552 380 - 500 V, VLT 5032 - 5052200 - 240 V AC and VLT 5042-5602, 525-690 V,please refer to Technical data and Installation regardingmechanical and electrical installation.Fig. 1■ 1. Mechanical InstallationVLT 5000 frequency converters allow side-by-side mounting. The necessary cooling demands a free airpassage of 100 mm above and below the frequency converter (5016-5062 380-500 V, 5008-5027 200-240V and 5016-5062 525-600 V must have 200 mm, 5072-5102, 380-500 V 225 mm).Drill all holes by using the measurements stated in the table. Please note the difference in unit voltage. Placethe frequency converter on the wall. Tighten up all four screws.All the below listed measurements are in mmVLT type A B C a bBookstyle IP 20, 200–240 V, (Fig. 2)5001 - 5003 395 90 260 384 705004 - 5006 395 130 260 384 70Bookstyle IP 20, 380–500 V (Fig. 2)5001 - 5005 395 90 260 384 705006 - 5011 395 130 260 384 70Compact IP 54, 200–240 V (Fig. 3)5001 - 5003 460 282 195 260 2585004 - 5006 530 282 195 330 2585008 - 5011 810 350 280 560 3265016 - 5027 940 400 280 690 375Compact IP 54, 380–500 V (Fig. 3)5001 - 5005 460 282 195 260 2585006 - 5011 530 282 195 330 2585016 - 5027 810 350 280 560 3265032 - 5062 940 400 280 690 3755072 - 5102 940 400 360 690 375Compact IP 20, 200–240 V (Fig. 4)5001 - 5003 395 220 160 384 2005004 - 5006 395 220 200 384 2005008 560 242 260 540 2005011 - 5016 700 242 260 680 2005022 - 5027 800 308 296 780 270Compact IP 20, 380–500 V (Fig. 4)5001 - 5005 395 220 160 384 2005006 - 5011 395 220 200 384 2005016 - 5022 560 242 260 540 2005027 - 5032 700 242 260 680 2005042 - 5062 800 308 296 780 2705072 - 5102 800 370 335 780 330Fig. 2Fig. 3Fig. 4MG.51.A9.02 - VLT is a registered Danfoss trademark6