VLT ® 5000 SeriesSpecialfunctions■ Local and remote controlThe frequency converter can be operatedmanually or remotely. The following is a list of thefunctions/commands given via the control panel,the digital inputs or the serial communication portin the two situations (modes).If parameter 002 is set to Local [1]:On the LCP, the following keys can be used for local control:Key: Parameter: Data value:[STOP] 014 [1] Enable[JOG] 015 [1] Enable[RESET] 017 [1] Enable[FWD/REV] 016 [1] EnableSet parameter 013 for LCP control and open loop [1] or LCP control as parameter 100 [3]:1. Local reference is set in parameter 003; can be changed via the "+/-" keys.2. Reversing can be effected by means of the [FWD/REV] key.Set parameter 013 for LCP digital control and open loop [2] or LCP digital control as parameter 100 [4]:For the above parameter setting, it is now possibleto control the frequency converter as follows:Digital inputs:1. Local reference set in parameter 003 can bechanged via the "+/-" keys.2. Reset via digital terminal 16, 17, 29, 32 or 33.3. Stop inverse via digital terminal 16, 17,27, 29, 32 or 33.4. Choice of Setup, lsb via digital terminal 16, 29 or 32.5. Choice of Setup, msb via digital terminal 17, 29 or 33.6. Ramp 2 via digital terminal 16, 17, 29, 32 or 33.7. Quick-stop via digital terminal 27.8. DC braking via digital terminal 27.9. Reset and motor coasting stop via digital terminal 27.10. Motor coasting stop via digital terminal 27.11. Reversing via digital terminal 19.12. Choice of Setup, msb/speed up via digitalterminal 32.13. Choice of Setup, lsb/speed down viadigital terminal 33.The serial communication port:1. Ramp 22. Reset3. Choice of Setup, lsb4. Choice of Setup, msb5. Relay 016. Relay 04If parameter 002 is set to Remote control [0]:Key: Parameter: Data value:[STOP] 014 [1][JOG] 015 [1][RESET] 017 [1]MG.51.A9.02 - VLT is a registered Danfoss trademark 79