VLT ® 5000 SeriesFunction:This parameter defines the Setup number to controlthe functions of the frequency converter.All parameters can be programmed in four individualparameter Setups, Setup 1 - Setup 4. In addition, thereis a Factory Setup, which cannot be modified.Description of choice:Factory Setup [0] contains the data set at the works.Can be used as a data source if the other Setupsare to be returned to a known state.Parameter 005 and 006 allow copying from oneSetup to one or all the other Setups.Setups 1-4 [1]-[4] are four individual Setups thatcan be selected individually.Multi-Setup [5] is used by remote-switchingbetween Setups. Terminals 16/17/29/32/33 aswell as the serial communication port can be usedfor switching between Setups.005 Programming Setup(EDIT SETUP)Value:Factory Setup (FACTORY SETUP) [0]Setup 1 (SETUP 1) [1]Setup 2 (SETUP 2) [2]Setup 3 (SETUP 3) [3]Setup 4 (SETUP 4) [4]✭Active Setup (ACTIVE SETUP) [5]Function:The choice is of the Setup in which programming(change of data) is to occur during operation(applies both via the control panel and via theserial communication port). The 4 Setups can beprogrammed independently of the Setup selected asthe active Setup (selected in parameter 004).Description of choice:The Factory Setup [0] contains the data set at theworks and can be used as a data source if the otherSetups are to be returned to a known state.Setups 1-4 [1]-[4] are individual Setups which can beused as required. They can be programmed freely,regardless of the Setup selected as the active Setup andthus controlling the functions of the frequency converter.NB!:If a general change of data or a copying tothe active Setup is effected, this immediatelyaffects the functioning of the unit.006 Copying of Setups(SETUP COPY)Value:✭No copying (NO COPY) [0]Copy to Setup 1 from # (COPY TO SETUP 1) [1]Copy to Setup 2 from # (COPY TO SETUP 2) [2]Copy to Setup 3 from # (COPY TO SETUP 3) [3]Copy to Setup 4 from # (COPY TO SETUP 4) [4]Copy to Setup all from # (COPY TO ALL) [5]# = the Setup selected in parameter 005Function:A copy is made from the Setup selected in parameter005 to one of the other Setups or to all the otherSetups simultaneously. The setup copying functiondoes not copy parameter 001, 004, 005, 500 and 501.Copying is only possible in Stop Mode (motorstopped on a Stop command).Description of choice:The copying starts when the desired copyingfunction has been entered and confirmed bypressing the [OK] key.The display indicates when copying is in progress.007 LCP copy(LCP COPY)Value:✭No copying (NO COPY) [0]Upload all parameters (UPLOAD ALL PARAM) [1]Download all parameters (DOWNLOAD ALL) [2]Download power-independent par.(DOWNLOAD SIZE INDEP.) [3]Function:Parameter 007 is used if it is desired to use theintegrated copying function of the control panel. Thecontrol panel is detachable. You can therefore easilycopy parameter value(s) from one to another.Description of choice:Select Upload all parameters [1] if all parameter valuesare to be transmitted to the control panel.Select Download all parameters [2] if all transmittedparameter values are to be copied to the frequencyconverter on which the control panel has been mounted.Select Download power-independent par. [3] if only thepower-independent parameters are to be downloaded.This is used if downloading to a frequency converter✭ = factory setting. () = display text [] = value for use in communication via serial communication portMG.51.A9.02 - VLT is a registered Danfoss trademark98