The SmartStart configures the frequency converter in 3phases, each consisting of several steps, see Table 5.6.Phase Comment1 Basic Programming Program e.g. motor data2 Application SectionSelect and programappropriate application:• Single pump/motor• Motor alternation• Basic cascade control• Master/follower3 Water and Pump Features Go to water and pumpdedicated parametersTable 5.6 SmartStart, Setup in 3 Phases5.4.2 Commissioning via [Main Menu]Recommended parameter settings are intended for start-up and checkout purposes. Application settings may vary.Enter data with power ON, but before operating thefrequency converter.1. Press [Main Menu] on the LCP.2. Press the navigation keys to scroll to parametergroup 0-** Operation/Display and press [OK].130BP066.101107 RPM0 - ** Operation/Display1 - ** Load/Motor2 - ** Brakes3 - ** Reference / Ramps3.84 A 1 (1)Main menuIllustration 5.2 Main Menu3. Press navigation keys to scroll to parametergroup 0-0* Basic Settings and press [OK].0-**Operation / Display0.0%0-0* Basic Settings0-1 * Set-up Operations0-2 * LCP Display0-3 * LCP Custom Readout0.00A 1(1)130BP087.10Illustration 5.3 Operation/Display4. Press navigation keys to scroll to 0-03 RegionalSettings and press [OK].0-0*Basic Settings0.0%0-03 Regional Settings[0] International0.00A 1(1)130BP088.10Illustration 5.4 Basic Settings5. Press navigation keys to select [0] International or[1] North America as appropriate and press [OK].(This changes the default settings for a numberof basic parameters).6. Press [Main Menu] on the LCP.7. Press the navigation keys to scroll to0-01 Language.8. Select language and press [OK].9. If a jumper wire is in place between controlterminals 12 and 27, leave 5-12 Terminal 27 DigitalInput at factory default. Otherwise, select NoOperation in 5-12 Terminal 27 Digital Input. Forfrequency converters with an optional bypass, nojumper wire is required between controlterminals 12 and 27.10. 3-02 Minimum Reference11. 3-03 Maximum Reference12. 3-41 Ramp 1 Ramp Up Time13. 3-42 Ramp 1 Ramp Down Time14. 3-13 Reference Site. Linked to Hand/Auto LocalRemote.5.4.3 Asynchronous Motor SetupEnter the motor data in parameter 1-20 Motor Power [kW]or 1-21 Motor Power [HP] to 1-25 Motor Nominal Speed. Theinformation can be found on the motor nameplate.1. 1-20 Motor Power [kW] or 1-21 Motor Power [HP]2. 1-22 Motor Voltage3. 1-23 Motor Frequency4. 1-24 Motor Current5. 1-25 Motor Nominal SpeedCommissioning VLT® AQUA Drive FC 202 Operating Instructions24 MG20MA02 - Rev. 2013-10-2955