8.2 Mains SupplyMains supply (L1, L2, L3)Supply voltage 200-240 V ±10%Supply voltage 380-480 V ±10%Supply voltage 525-600 V ±10%Supply voltage 525-690 V ±10%Mains voltage low/mains drop-out:During low mains voltage or a mains drop-out, the frequency converter continues until the intermediate circuit voltage dropsbelow the minimum stop level, which corresponds typically to 15% below the lowest rated supply voltage of the frequencyconverter. Power-up and full torque cannot be expected at mains voltage lower than 10% below the lowest rated supply voltageof the frequency converter.Supply frequency 50/60 Hz +4/-6%The frequency converter power supply is tested in accordance with IEC61000-4-28, 50 Hz +4/-6%.Max. imbalance temporary between mains phases 3.0% of rated supply voltageTrue Power Factor (λ) ≥ 0.9 nominal at rated loadDisplacement Power Factor (cosφ) near unity (> 0.98)Switching on input supply L1, L2, L3 (power-ups) ≤ 7.5 kW maximum 2 times/min.Switching on input supply L1, L2, L3 (power-ups) 11-90 kW maximum 1 time/min.Environment according to EN60664-1 overvoltage category III/pollution degree 2The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480/600/690V maximum.8.3 Motor Output and Motor DataMotor output (U, V, W)Output voltage 0-100% of supply voltageOutput frequency 0-590 Hz*Switching on output UnlimitedRamp times 1-3600 s* Dependent on power size.Torque characteristicsStarting torque (Constant torque) maximum 110% for 1 min.*Starting torque maximum 135% up to 0.5 s*Overload torque (Constant torque) maximum 110% for 1 min.**Percentage relates to the nominal torque of the frequency converter.Specifications VLT® AQUA Drive FC 202 Operating InstructionsMG20MA02 - Rev. 2013-10-29 518 8