4.1.7 5-** Digital In/OutPar.No. #Parameter description Default value 4-set-up FC 302onlyChangeduringoperationConver-sionindexType5-0* Digital I/O mode5-00 Digital I/O Mode [0] PNP - Active at 24V All set-ups FALSE - Uint85-01 Terminal 27 Mode [0] Input All set-ups TRUE - Uint85-02 Terminal 29 Mode [0] Input All set-ups TRUE - Uint85-1* Digital Inputs5-10 Terminal 18 Digital Input ExpressionLimit All set-ups TRUE - Uint85-11 Terminal 19 Digital Input ExpressionLimit All set-ups TRUE - Uint85-12 Terminal 27 Digital Input ExpressionLimit All set-ups TRUE - Uint85-13 Terminal 29 Digital Input ExpressionLimit All set-ups TRUE - Uint85-14 Terminal 32 Digital Input ExpressionLimit All set-ups TRUE - Uint85-15 Terminal 33 Digital Input ExpressionLimit All set-ups TRUE - Uint85-16 Terminal X30/2 Digital Input ExpressionLimit All set-ups TRUE - Uint85-17 Terminal X30/3 Digital Input ExpressionLimit All set-ups TRUE - Uint85-18 Terminal X30/4 Digital Input ExpressionLimit All set-ups TRUE - Uint85-19 Terminal 37 Digital Input [1] Safe Stop Alarm 1 set-up TRUE - Uint85-20 Terminal X46/1 Digital Input ExpressionLimit All set-ups TRUE - Uint85-21 Terminal X46/3 Digital Input ExpressionLimit All set-ups TRUE - Uint85-22 Terminal X46/5 Digital Input ExpressionLimit All set-ups TRUE - Uint85-23 Terminal X46/7 Digital Input ExpressionLimit All set-ups TRUE - Uint85-24 Terminal X46/9 Digital Input ExpressionLimit All set-ups TRUE - Uint85-25 Terminal X46/11 Digital Input ExpressionLimit All set-ups TRUE - Uint85-26 Terminal X46/13 Digital Input ExpressionLimit All set-ups TRUE - Uint85-3* Digital Outputs5-30 Terminal 27 Digital Output [0] No operation All set-ups TRUE - Uint85-31 Terminal 29 Digital Output [0] No operation All set-ups TRUE - Uint85-32 Term X30/6 Digi Out (MCB 101) [0] No operation All set-ups TRUE - Uint85-33 Term X30/7 Digi Out (MCB 101) [0] No operation All set-ups TRUE - Uint85-4* Relays5-40 Function Relay ExpressionLimit All set-ups TRUE - Uint85-41 On Delay, Relay 0.01 s All set-ups TRUE -2 Uint165-42 Off Delay, Relay 0.01 s All set-ups TRUE -2 Uint165-5* Pulse Input5-50 Term. 29 Low Frequency 100 Hz All set-ups TRUE 0 Uint325-51 Term. 29 High Frequency 100 Hz All set-ups TRUE 0 Uint325-52 Term. 29 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int325-53 Term. 29 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int325-54 Pulse Filter Time Constant #29 100 ms All set-ups FALSE -3 Uint165-55 Term. 33 Low Frequency 100 Hz All set-ups TRUE 0 Uint325-56 Term. 33 High Frequency 100 Hz All set-ups TRUE 0 Uint325-57 Term. 33 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int325-58 Term. 33 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int325-59 Pulse Filter Time Constant #33 100 ms All set-ups FALSE -3 Uint165-6* Pulse Output5-60 Terminal 27 Pulse Output Variable [0] No operation All set-ups TRUE - Uint85-62 Pulse Output Max Freq #27 5000 Hz All set-ups TRUE 0 Uint325-63 Terminal 29 Pulse Output Variable [0] No operation All set-ups TRUE - Uint85-65 Pulse Output Max Freq #29 5000 Hz All set-ups TRUE 0 Uint325-66 Terminal X30/6 Pulse Output Variable [0] No operation All set-ups TRUE - Uint85-68 Pulse Output Max Freq #X30/6 5000 Hz All set-ups TRUE 0 Uint32Parameter Lists Programming Guide206 Danfoss A/S © Rev. 2014-01-21 All rights reserved. MG20O70244