3.8 Parameters 6-** Analog In/Out3.8.1 6-0* Analog I/O ModeParameter group for setting up the analog I/O configu-ration.The frequency converter is equipped with 2 analog inputs:Terminal 53 and 54. The analog inputs can freely beallocated to either voltage (0-10 V) or current input (0/4-20mA)NOTICEThermistors may be connected to either an analog or adigital input.6-00 Live Zero Timeout TimeRange: Function:10 s* [1 -99 s]Enter the Live Zero Time-out time period. LiveZero Time-out Time is active for analog inputs, i.e.terminal 53 or terminal 54, used as reference orfeedback sources. If the reference signal valueassociated with the selected current input fallsbelow 50% of the value set inparameter 6-10 Terminal 53 Low Voltage,parameter 6-12 Terminal 53 Low Current,parameter 6-20 Terminal 54 Low Voltage orparameter 6-22 Terminal 54 Low Current for a timeperiod longer than the time set inparameter 6-00 Live Zero Timeout Time, the functionselected in parameter 6-01 Live Zero TimeoutFunction is activated.6-01 Live Zero Timeout FunctionOption: Function:Select the time-out function. The function set inparameter 6-01 Live Zero Timeout Function isactivated if the input signal on terminal 53 or54 is below 50% of the value inparameter 6-10 Terminal 53 Low Voltage,parameter 6-12 Terminal 53 Low Current,parameter 6-20 Terminal 54 Low Voltage orparameter 6-22 Terminal 54 Low Current for atime period defined in parameter 6-00 Live ZeroTimeout Time. If several time-outs occur simulta-neously, the frequency converter prioritises thetime-out functions as follows1. Parameter 6-01 Live Zero TimeoutFunction2. Parameter 8-04 Control TimeoutFunctionThe output frequency of the frequencyconverter can be:6-01 Live Zero Timeout FunctionOption: Function:• [1] frozen at the present value• [2] overruled to stop• [3] overruled to jog speed• [4] overruled to max. speed• [5] overruled to stop with subsequenttrip[0] Off[1] Freezeoutput[2] Stop[3] Jogging[4] Max. speed[5] Stop andtripRef./Feedback[RPM]Analog inputHigh Ref./Feedb. Value'Low Ref./Feedb. Value''Low Voltage'or'Low Current''High Voltage'or'High Current'130BA038.131 V 5 V 10 V30060090012001500[V]150Par 6-xxPar 6-xxPar 6-xxPar 6-xxIllustration 3.30 Live Zero Conditions3.8.2 6-1* Analog Input 1Parameters for configuring the scaling and limits foranalog input 1 (terminal 53).6-10 Terminal 53 Low VoltageRange: Function:0.07 V* [ 0 - par.6-11 V]Enter the low voltage value. This analoginput scaling value should correspond tothe low reference/feedback value set inparameter 6-14 Terminal 53 Low Ref./Feedb.Value.Parameter Description Programming GuideMG20O702 Danfoss A/S © Rev. 2014-01-21 All rights reserved. 813 3