3.7 Parameters: 6-** Analog In/OutParameter group for setting up the analog I/O configu-ration and the digital output. The frequency converter isequipped with 2 analog inputs: Terminal 53 and 54. Theanalog inputs can freely be allocated to either voltage(0-10 V) or current input (0/4-20 mA)3.7.1 6-0* Analog I/O Mode6-00 Live Zero Timeout TimeRange: Function:10 s* [1 - 99 s] Enter the time-out time.6-01 Live Zero Timeout FunctionOption: Function:Select the time-out function. The function setin 6-01 Live Zero Timeout Function will beactivated if the input signal on terminal 53 or54 is below 50% of the value in 6-10 Terminal53 Low Voltage, 6-12 Terminal 53 Low Current,6-20 Terminal 54 Low Voltage or 6-22 Terminal54 Low Current for a time period defined in6-00 Live Zero Timeout Time.[0] Off[1] Freeze output[2] Stop[3] Jogging[4] Max. speed[5] Stop and tripRef./FeedbackAnalog inputHigh Ref./Feedb. Value'Low Ref./Feedb. Value''Low Voltage'or'Low Current''High Voltage'or'High Current'130BD378.101 V 5 V 10 V30060090012001500[V]150Par 6-xxPar 6-xxPar 6-xxPar 6-xxIllustration 3.16 Time-out Function3.7.2 6-1* Analog Input 53Parameters for configuring the scaling and limits foranalog input 53 (terminal 53).6-10 Terminal 53 Low VoltageRange: Function:0.07 V* [0 - 10 V] Enter the voltage (V) that corresponds to6-14 Terminal 53 Low Ref./Feedb. Value. Thevalue must be set at >1 V in order toactivate 6-01 Live Zero Timeout Function.6-11 Terminal 53 High VoltageRange: Function:10 V* [0 - 10 V] Enter the voltage (V) that corresponds to thehigh reference value (set in 6-15 Terminal 53High Ref./Feedb. Value).6-12 Terminal 53 Low CurrentRange: Function:4 mA* [0 - 20mA]Enter the low current value. This referencesignal should correspond to the lowreference/feedback value, set in 6-14 Terminal53 Low Ref./Feedb. Value. The value must beset at >2 mA in order to activate the LiveZero Time-out Function in 6-01 Live ZeroTimeout Function.6-13 Terminal 53 High CurrentRange: Function:20 mA* [0 - 20 mA] Enter the high current valuecorresponding to the high reference/feedback set in 6-15 Terminal 53 High Ref./Feedb. Value.6-14 Terminal 53 Low Ref./Feedb. ValueRange: Function:0 * [-4999 - 4999 ] Enter the reference or feedback value thatcorresponds to the voltage or current set inparameters 6-10 to 6-12.6-15 Terminal 53 High Ref./Feedb. ValueRange: Function:Size related* [-4999 -4999 ]Enter the reference or feedbackvalue that corresponds to thevoltage or current set inparameters 6-11 to 6-13.6-16 Terminal 53 Filter Time ConstantRange: Function:0.01 s* [0.01 - 10s]Enter the time constant. This is a first-orderdigital low pass filter time constant forsuppressing electrical noise in terminal 53.A high time constant value improvesParameter Descriptions VLT® AutomationDrive FC 360 Programming Guide48 MG06C102 - VLT® is a registered Danfoss trademark33