3.2 Hand On/Auto On ModeAfter installation (see chapter 4 Installation), there are 2simple ways to start up the frequency converter: Hand Onand Auto On mode. At the first power-up, it is in Auto Onmode.130BD062.10D HandOn ResetAutoOnOKOnWarnAlarmIllustration 3.3 Location of Hand On, Off/Reset and Auto OnKeys on the NLCP• Press [Hand On] to provide a local start commandto the frequency converter. Press [▲] and [▼] toincrease and decrease speed.• Press [Off/Reset] to stop the frequency converter.• Press [Auto On] to control the frequencyconverter either via control terminals or serialcommunication.CAUTIONSince the frequency converter is in Auto On mode at firstpower-up, the frequency converter may start the motordirectly.NOTICE5-12 Terminal 27 Digital Input has coast inverse as defaultsetting. Connect terminals 12 and 27 to test Hand On/Auto On running.For LCP operation, see chapter 5 Local Control Panel andProgramming.3.3 Application SelectionsUse the selections for quick application set-up of the mostcommon applications by setting 0-16 Application Selection.When necessary, the selections can be modified forindividual needs. All selections are for Auto On mode.NOTICEWhen an application is selected, relevant parameters areautomatically set. Customer specific configuration of allparameters based on specific requirements is stillpossible.CAUTIONIf any of the applications below are selected, relay 1 isset to [Running] and relay 2 is set to [Alarm]ApplicationPumps, fans, compressorsDescriptionFor applications where a value (e.g. pressure, temperature) mustbe kept at a desired level by sensor feedback130BC430.10+24V 12DI1 18DI2 19DI3 27DI4 29DI5 32DI6 33DI7 31COM 20+10V 50AI1 53 - +AI2 54COM 55AO1 45AO2 42123456R1R2FC 360StartCoast inverseJog4-20mAParameter settingsParameter Option/value1-00 Configuration Mode [3] Process Closed Loop1-03 Torque Characteristics [1] Variable Torque3-00 Reference Range [0] Min- Max3-15 Reference 1 Source [0] No Function4-12 Motor Speed Low Limit [Hz] 30.0 Hz4-14 Motor Speed High Limit [Hz] 50.0 Hz5-10 Terminal 18 Digital Input [8] StartQuick Start Quick Guide10 Danfoss A/S © Rev. 06/2014 All rights reserved. MG06A50233