input, motor, and grounding for enclosure type J7. Actualconfigurations vary with unit types and optionalequipment.4.2.4 Control WiringAccess• Remove the cover plate with a screwdriver. SeeIllustration 4.6.130BC504.10Illustration 4.6 Control Wiring Access for J1–J7 EnclosuresControl Terminal TypesIllustration 4.7 shows the frequency converter controlterminals. Terminal functions and default settings aresummarised in Table 4.2.42 4512 18 19 27 29 31 32 33 20 50 53 54 55130BC505.12Illustration 4.7 Control Terminal LocationsSee chapter 8.2 General Technical Data for terminal ratingsdetails.Terminal Para-meterDefaultsetting DescriptionDigital I/O, Pulse I/O, Encoder12 – +24 V DC24 V DC supplyvoltage. Maximumoutput current is 100mA for all 24 V loads.18 5-10 [8] Start Digital inputs.19 5-11 [10] Reversing31 5-16 [0] Nooperation Digital input32 5-14 [0] NooperationDigital input, 24 Vencoder. Terminal 33can be used for pulseinput.33 5-15 [0] Nooperation27 5-125-30DI [2] CoastinverseDO [0] NooperationSelectable for eitherdigital input, digitaloutput or pulseoutput. Default settingis digital input.Terminal 29 can beused for pulse input.29 5-135-31DI [14] JogDO [0] Nooperation20 –Common for digitalinputs and 0 Vpotential for 24 Vsupply.Analog inputs/outputs42 6-91 [0] NooperationProgrammable analogoutput. The analogsignal is 0-20 mA or4-20 mA at amaximum of 500 Ω.Can also beconfigured as digitaloutputs45 6-71 [0] Nooperation50 – +10 V DC10 V DC analog supplyvoltage. 15 mAmaximum commonlyused for potenti-ometer or thermistor.53 6-1* ReferenceAnalog input.Selectable for voltageor current.54 6-2* Feedback55 – Common for analoginputInstallation Quick Guide20 Danfoss A/S © Rev. 06/2014 All rights reserved. MG06A50244