Enclosure Power[kW]Height[mm]Width[mm]Depth[mm]Mounting hole[mm] Max. weightFrame IPclass3x200-240V3x380-480V3x525-600V AA inclDecouplingplatea B b C d e f KgH6 20 15-18.5 30-45 22-30 518 595-635 495 239 200 242 - 8.5 15 24.5H7 20 22-30 55-75 45-55 550 630-690 521 313 270 335 - 8.5 17 36H8 20 37-45 90 75-90 660 800 631 375 330 335 - 8.5 17 51H9 20 - - 2.2-7.5 268 374 257 130 110 205 11 5.5 9.0 6.6H10 20 - - 11-15 399 419 380 165 140 248 12 6.8 7.9 12.0I6 54 - 22-37 - 650 - 624 242 210 260 19 9.0 9.0 27.0I7 54 - 45-55 - 680 - 648 308 272 310 19 9.0 9.8 45.0I8 54 - 75-90 - 770 - 739 370 334 335 19 9.0 9.8 65.0The above mentioned dimensions are only for the physicalunits, but when installing in an application it is necessaryto add space for free air passage both above and belowthe units. The amount of space for free air passage is listedin the following table:Enclosure Clearance needed for free air passage [mm]Frame IP class Above unit Below unitH6 20 200 200H7 20 200 200H8 20 225 225H9 20 100 100H10 20 200 200I6 54 200 200I7 54 200 200I8 54 225 2255.1.1 Side-by-Side InstallationThe frequency converter can be mounted side-by-side and requires the clearance above and below for cooling.Power Clearance above/below (mm/inch)Frame IP class 3x200-240V 3 x 380-480V 3 x 525-600VH1 IP20 0.25-1.5kW/0.33-2Hp 0.37-1.5kW/0.5-2Hp 100/4H2 IP20 2.2kW/3Hp 2.2-4kW/3-5.4Hp 100/4H3 IP20 3.7kW/5Hp 5.5-7.5 kW/7.5-10 Hp 100/4H4 IP20 5.5-7.5kW/7.5-10Hp 11-15kW/15-20Hp 100/4H5 IP20 11kW/15 Hp 18.5-22kW/25-30Hp 100/4H6 IP20 15-18.5Kw/20-25Hp 30-45kW/40-60Hp 22-30kW/30-40Hp 200/7.9H7 IP20 22-30kW/30-40Hp 55-75kW/100-120Hp 45-55kW/60-100Hp 200/7.9H8 IP20 37-45kW/50-60Hp 90kW/125Hp 75-90kW/120-125Hp 225/8.9H9 IP20 2.2-7.5kW/3-10Hp 100/4H10 IP20 11-15kW/15-20Hp 200/7.9NOTEWith IP21/Nema Type1 option kit mounted, a distance of 50mm between the units is required.How to Install VLT HVAC Basic Drive Design Guide46 MG.18.C2.02 - VLT® is a registered Danfoss trademark55