8.1.3 Mains Supply 3 x 380-480VACFrequency converter P22K P30K P37K P45K P55K P75K P90KTypical shaft output (kW) 22.0 30.0 37.0 45.0 55.0 75.0 90.0Typical shaft output (hp) 30.0 40.0 50.0 60.0 70.0 100.0 125.0IP54 frame I6 I6 I6 I7 I7 I8 I8Max. cable size in terminals (mains, motor) [mm2/AWG] 35/2 35/2 35/2 50/1 50/1 95/(3/0) 120/(4/0)Output currentRELAY 2130BB632.1040°C ambient temperatureContinuous(3x380-440V)[A]44.0 61.0 73.0 90.0 106.0 147.0 177.0Intermittent(3x380-440V)[A]48.4 67.1 80.3 99.0 116.6 161.7 194.7Continuous(3x440-480V)[A]40.0 52.0 65.0 80.0 105.0 130.0 160.0Intermittent(3x440-480V)[A]44.0 57.2 71.5 88.0 115.5 143.0 176.0Max. input currentRELAY 2130BB633.10Continuous(3x380-440V)[A]41.8 57.0 70.3 84.2 102.9 140.3 165.6Intermittent(3x380-440V)[A]46.0 62.7 77.4 92.6 113.1 154.3 182.2Continuous(3x440-480V)[A]36.0 49.2 60.6 72.5 88.6 120.9 142.7Intermittent(3x440-480V)[A]39.6 54.1 66.7 79.8 97.5 132.9 157.0Max. mains fusesFrequency converter P22K P30K P37K P45K P55K P75K P90KEstimated power loss [W], Best case/typical1) 496 734 705 927 1075 1425 1469Weight enclosure IP54kg] 27 27 27 45 45 65 65Efficiency [%], Best case/Typical 1 98.0 97.8 98.3 98.3 98.3 98.3 98.5Output current50°C ambient temperatureContinuous(3x380-440V) [A]35.2 48.8 58.4 63.0 74.2 102.9 123.9Intermittent(3x380-440V) [A]38.7 53.9 64.2 69.3 81.6 113.2 136.3Continuous(3x440-480V) [A]32.0 41.6 52.0 56.0 73.5 91.0 112.0Intermittent(3x440-480V) [A]35.2 45.8 57.2 61.6 80.9 100.1 123.2General Specifications and ... VLT HVAC Basic Drive Design Guide84 MG.18.C2.02 - VLT® is a registered Danfoss trademark88