6.4 Quick Transfer of Parameter Settingsbetween Multiple Frequency ConvertersOnce the set-up of a frequency converter is complete,Danfoss recommends that you store the data in the LCP oron a PC via MCT 10 Set-up Software tool.Data storage in LCP.1. Go to 0-50 LCP Copy2. Press the [OK] key3. Select “All to LCP”4. Press the [OK] keyWARNINGStop the motor before performing this operation.You can now connect the LCP to another frequencyconverter and copy the parameter settings to thisfrequency converter as well.Data transfer from LCP to frequency converter:1. Go to 0-50 LCP Copy2. Press the [OK] key3. Select “All from LCP”4. Press the [OK] keyNOTEStop the motor before performing this operation.6.5 Read-out and Programming of IndexedParametersUse 3-10 Preset Reference as an example.Choose the parameter, press [OK], and use the up/downnavigation keys to scroll through the indexed values. Tochange the parameter value, select the indexed value andpress [OK]. Change the value by using the up/down keys.Press [OK] to accept the new setting. Press [CANCEL] toabort. Press [Back] to leave the parameter.6.6 Initialise the Frequency Converter toDefault Settings in two WaysRecommended initialisation (via 14-22 Operation Mode)1. Select 14-22 Operation Mode.2. Press [OK].3. Select Initialisation and Press [OK].4. Cut off the mains supply and wait until thedisplay turns off.5. Reconnect the mains supply - the frequencyconverter is now reset. Except the followingparameters.8-30 Protocol8-31 Address8-32 Baud Rate8-33 Parity / Stop Bits8-35 Minimum Response Delay8-36 Maximum Response Delay8-37 Maximum Inter-char delay8-70 BACnet Device Instance8-72 MS/TP Max Masters8-73 MS/TP Max Info Frames8-74 "I am" Service8-75 Intialisation Password15-00 Operating Hours to 15-05 Over Volt's15-03 Power Up's15-04 Over Temp's15-05 Over Volt's15-30 Alarm Log: Error Code15-4* Drive identification parameters1-06 Clockwise DirectionHow to Programme VLT HVAC Basic Drive Design Guide62 MG.18.C2.02 - VLT® is a registered Danfoss trademark66