The FC 101 Start-up Wizard for Open Loop ApplicationsNo & Name Range Default Function0-03 Regional Settings [0] International[1] US00-06 Grid Type 0] 200-240V/50Hz/IT-grid[1] 200-240V/50Hz/Delta[2] 200-240V/50Hz[10] 380-440V/50Hz/IT-grid[11] 380-440V/50Hz/Delta[12] 380-440V/50Hz[20] 440-480V/50Hz/IT-grid[21] 440-480V/50Hz/Delta[22] 440-480V/50Hz[30] 525-600V/50Hz/IT-grid[31] 525-600V/50Hz/Delta[32] 525-600V/50Hz[100] 200-240V/60Hz/IT-grid[101] 200-240V/60Hz/Delta[102] 200-240V/60Hz[110] 380-440V/60Hz/IT-grid[111] 380-440V/60Hz/Delta[112] 380-440V/60Hz[120] 440-480V/60Hz/IT-grid[121] 440-480V/60Hz/Delta[122] 440-480V/60Hz[130] 525-600V/60Hz/IT-grid[131] 525-600V/60Hz/Delta[132] 525-600V/60HzSize related Select operating mode for restart uponreconnection of the drive to mains voltage afterpower down1-20 Motor Power 0.12-110kW/0.16-150hp Size related Enter motor power from nameplate data1-22 Motor Voltage 50.0 - 1000.0V Size related Enter motor voltage from nameplate data1-23 Motor Frequency 20.0 - 400.0Hz Size related Enter motor frequency from nameplate data1-24 Motor Current 0.01 - 10000.00A Size related Enter motor current from nameplate data1-25 Motor NominalSpeed100.0 - 9999.0 RPM Size related Enter motor nominal speed from nameplate data4-12 Motor Speed LowLimit [Hz]0.0 - 400 Hz 0 Hz Enter the minimum limit for low speed4-14 Motor Speed HighLimit [Hz]0.0 - 400 Hz 65 Hz Enter the maximum limit for high speed3-41 Ramp 1 Ramp upTime0.05 - 3600.0 s Size related Ramp up time from 0 to rated 1-23 MotorFrequency3-42 Ramp 1 RampDown Time0.05 - 3600.0 s Size related Ramp down time from rated 1-23 Motor Frequencyto 01-73 Flying Start [0] Disabled[1] Enabled0 Select Enable to enable the frequency converter tocatch a spinning motor i.e. fan applications6-19 Terminal 53 mode [0] Current[1] Voltage1 Select if terminal 53 is used for current- or voltageinput6-10 Terminal 53 LowVoltage0-10V 0.07V Enter the voltage that corresponds to the lowreference value6-11 Terminal 53 HighVoltage0-10V 10V Enter the voltage that corresponds to the highreference value6-12 Terminal 53 LowCurrent0-20mA 4 Enter the current that corresponds to the lowreference value6-13 Terminal 53 HighCurrent0-20mA 20 Enter the current that corresponds to the highreference value3-02 Minimum Reference -4999-4999 0 The minimum reference is the lowest valueobtainable by summing all referencesHow to Programme VLT HVAC Basic Drive Design GuideMG.18.C2.02 - VLT® is a registered Danfoss trademark 576 6