1. Use a clamp from the accessory bag to connectthe shield to the Adjustable frequency drivedecoupling plate for control cables.See section entitled 5.7.3 Grounding of Shielded/ArmoredControl Cables for the correct termination of control cables.130BA681.10Figure 5.265.2.14 Switches S201, S202, and S801Switches S201 (A53) and S202 (A54) are used to select acurrent (0–20 mA) or a voltage (0–10 V) configuration ofthe analog input terminals 53 and 54 respectively.Switch S801 (BUS TER.) can be used to enable terminationon the RS-485 port (terminals 68 and 69).See Figure 5.25Default setting:S201 (A53) = OFF (voltage input)S202 (A54) = OFF (voltage input)S801 (Bus termination) = OFFNOTE!It is recommended to only change switch position atpower off.130BT310.101 2N OVLTBUS TER.OFF-ON A53 A54U- I U- IFigure 5.275.3 Final Set-Up and TestTo test the set-up and ensure that the Adjustablefrequency drive is running, follow these steps.Step 1. Locate the motor nameplateThe motor is either star- (Y) or delta-connected (Δ). Thisinformation is located on the motor nameplate data.Step 2. Enter the motor nameplate data in this parameterlist.To access this list, first press the [QUICK MENU] key, thenselect “Q2 Quick Set-up”.1. Motor Power [kW]or Motor Power [HP]1-20 Motor Power [kW]1-21 Motor Power [HP]2. Motor Voltage 1-22 Motor Voltage3. Motor Frequency 1-23 Motor Frequency4. Motor Current 1-24 Motor Current5. Motor Nominal Speed 1-25 Motor NominalSpeedTable 5.30How to Install VLT® HVAC Drive Design GuideMG11BB22 - VLT® is a registered Danfoss trademark 5-255 5