7.1.2 Adjustable Frequency Drive HardwareSetupUse the terminator dip switch on the main control boardof the Adjustable frequency drive to terminate the RS-485bus.1 2S801ON130BA272.11Figure 7.3 Terminator Switch Factory SettingThe factory setting for the dip switch is OFF.7.1.3 Adjustable Frequency DriveParameter Settings for ModbusCommunicationThe following parameters apply to the RS-485 interface(FC-port):Parameter Function8-30 Protocol Select the application protocol to run onthe RS-485 interface8-31 Address Set the node address. Note: The addressrange depends on the protocol selected in8-30 Protocol8-32 Baud Rate Set the baud rate. Note: The default baudrate depends on the protocol selected in8-30 Protocol8-33 Parity / StopBitsSet the parity and number of stop bits.Note: The default selection depends on theprotocol selected in 8-30 Protocol8-35 MinimumResponse DelaySpecify a minimum delay time betweenreceiving a request and transmitting aresponse. This can be used for overcomingmodem turnaround delays.8-36 MaximumResponse DelaySpecify a maximum delay time betweentransmitting a request and receiving aresponse.8-37 MaximumInter-Char DelaySpecify a maximum delay time betweentwo received bytes to ensure timeout iftransmission is interrupted.Table 7.27.1.4 EMC PrecautionsThe following EMC precautions are recommended in orderto achieve interference-free operation of the RS-485network.Relevant national and local regulations, for exampleregarding protective ground connection, must beobserved. The RS-485 communication cable must be keptaway from motor and brake resistor cables to avoidcoupling of high frequency noise from one cable toanother. Normally a distance of 200mm (8 inches) issufficient, but keeping the greatest possible distancebetween the cables is generally recommended, especiallywhere cables run in parallel over long distances. Whencrossing is unavoidable, the RS-485 cable must cross motorand brake resistor cables at an angle of 90 degrees.Serial com. bus cableBrake resistorMin. 200mm90° crossing130BA080.10Figure 7.4RS-485 Installation and Set... VLT® HVAC Drive Design Guide7-2 MG11BB22 - VLT® is a registered Danfoss trademark77