Line Power Supply 3 x 380–480 V ACP500 P560 P630 P710 P800 P1M0Typical shaft output at 400 V [kW] 500 560 630 710 800 1000Typical shaft output at 460 V [hp] 650 750 900 1000 1200 1350Enclosure protection rating IP21,IP54 without/with options cabinet F1/F3 F1/F3 F1/F3 F1/F3 F2/F4 F2/F4Output currentContinuous (at 400 V) [A] 880 990 1120 1260 1460 1720Intermittent (60 s overload)(at 400 V) [A] 968 1089 1232 1386 1606 1892Continuous (at 460/480 V) [A] 780 890 1050 1160 1380 1530Intermittent (60 s overload)(at 460/480 V) [A] 858 979 1155 1276 1518 1683Continuous KVA (at 400 V) [KVA] 610 686 776 873 1012 1192Continuous KVA (at 460 V) [KVA] 621 709 837 924 1100 1219Maximum input currentContinuous(at 400 V) [A] 857 964 1090 1227 1422 1675Continuous (at 460/480 V) [A] 759 867 1022 1129 1344 1490Maximum cable size, motor [mm2(AWG2))]8 x 150(8 x 300 mcm)12 x 150(12 x 300 mcm)Maximum cable size, line powerF1/F2 [mm2 (AWG2))]8 x 240(8 x 500 mcm)Maximum cable size, line powerF3/F4 [mm2 (AWG2))]8 x 456(8 x 900 mcm)Maximum cable size, load sharing[mm2 (AWG2))]4 x 120(4 x 250 mcm)Maximum cable size, brake [mm2(AWG2))4 x 185(4 x 350 mcm)6 x 185(6 x 350 mcm)Maximum external pre-fuses [A]1) 1600 2000 2500Estimated power loss at ratedmaximum load [W]3), 400 V, F1 &F210162 11822 12512 14674 17293 19278Estimated power loss at ratedmaximum load [W]3), 460 V, F1 &F28876 10424 11595 13213 16229 16624Maximum added losses of A1 RFI,circuit breaker or disconnect, &contactor, F3 & F4963 1054 1093 1230 2280 2541Maximum panel options losses 400Weight,enclosure protection rating IP21,IP54 [kg (lb)]1017/1318 (2242.1/2905.7) 1260/1561 (2778/3441.5)Weight rectifier module [kg (lb)] 102 (224.9) 136 (300)Weight inverter module [kg (lb)] 102 (224.9) 136 (300) 102 (224.9)Efficiency4) 0.98Output frequency 0–590 HzHeatsink overtemperature trip 95 °C (203 °F)Power card ambient trip 85 °C (185 °F)Table 7.2 Line Power Supply 3 x 380–480 V ACGeneral Specifications Instruction ManualMG11F522 Danfoss A/S © 08/2014 All rights reserved. 1197 7