6-01 Live Zero Timeout FunctionOption: Function:Select the Timeout function. The function setin parameter 6-01 Live Zero Timeout Functionwill be activated if the input signal onterminal 53 or 54 is below 50% of the valuein parameter 6-10 Terminal 53 Low Voltage,parameter 6-12 Terminal 53 Low Current,parameter 6-20 Terminal 54 Low Voltage orparameter 6-22 Terminal 54 Low Current for atime period defined in parameter 6-00 LiveZero Timeout Time. If several timeouts occursimultaneously, the adjustable frequency driveprioritizes the timeout functions as follows1. Parameter 6-01 Live Zero TimeoutFunction2. Parameter 8-04 Control TimeoutFunctionThe output frequency of the adjustablefrequency drive can be:• [1] frozen at the present value• [2] overruled to stop• [3] overruled to jog speed• [4] overruled to max. speed• [5] overruled to stop withsubsequent trip[0] * Off[1] Freezeoutput[2] Stop[3] Jogging[4] Max. speed[5] Stop andtripRef./Feedback[RPM]Analog inputHigh Ref./Feedb. Value'Low Ref./Feedb. Value''Low Voltage' or'Low Current''High Voltage' or'High Current'130BA038.131 V 5 V 10 V30060090012001500[V]150Par 6-xxPar 6-xxPar 6-xxPar 6-xxFigure 6.126-10 Terminal 53 Low VoltageRange: Function:0.07 V* [ 0 - par.6-11 V]Enter the low voltage value. This analoginput scaling value should correspond tothe low reference/feedback value set inparameter 6-14 Terminal 53 Low Ref./Feedb.Value.6-11 Terminal 53 High VoltageRange: Function:10 V* [ par. 6-10- 10 V]Enter the high voltage value. This analoginput scaling value should correspond to thehigh reference/feedback value set inparameter 6-15 Terminal 53 High Ref./Feedb.Value.6-14 Terminal 53 Low Ref./Feedb. ValueRange: Function:0* [-999999.999 -999999.999 ]Enter the analog input scaling value thatcorresponds to the low voltage/lowcurrent set in parameter 6-10 Terminal 53Low Voltage and parameter 6-12 Terminal53 Low Current.6-15 Terminal 53 High Ref./Feedb. ValueRange: Function:Size related* [-999999.999 - 999999.999 ]How to Program VLT® HVAC Drive FC 10296 Danfoss A/S © 08/2014 All rights reserved. MG11F52266