2 How to Programme2.1 Local Control Panel2.1.1 How to Operate Graphical LCP (GLCP)The following instructions are valid for the GLCP (LCP 102).The GLCP is divided into four functional groups:1. Graphical display with Status lines.2. Menu keys and indicator lights (LEDs) - selectingmode, changing parameters and switchingbetween display functions.3. Navigation keys and indicator lights (LEDs).4. Operation keys and indicator lights (LEDs).Graphical display:The LCD-display is back-lit with a total of 6 alpha-numericlines. All data is displayed on the LCP which can show upto five operating variables while in [Status] mode.Display lines:a. Status line: Status messages displaying icons andgraphics.b. Line 1-2: Operator data lines displaying data andvariables defined or chosen by the user. Bypressing the [Status] key, up to one extra line canbe added.c. Status line: Status messages displaying text.Autoon ResetHandon OffStatus QuickMenuMainMenuAlarmLogBackCancelInfoOKStatus 1(0)1234rpm 10,4A 43,5HzRun OK43,5HzOnAlarmWarn.130BA018.131234bacThe display is divided into 3 sections:Top section (a) shows the status when in status mode orup to 2 variables when not in status mode and in the caseof Alarm/Warning.The number of the Active Set-up (selected as the ActiveSet-up in 0-10 Active Set-up) is shown. When programmingin another Set-up than the Active Set-up, the number ofthe Set-up being programmed appears to the right inbrackets.The Middle section (b) shows up to 5 variables with relatedunit, regardless of status. In case of alarm/warning, thewarning is shown instead of the variables.How to Programme VLT® HVAC Drive Programming GuideMG.11.CC.02 - VLT® is a registered Danfoss trademark 92 2