3.16 Main Menu - Data Readouts - Group 1616-00 Control WordRange: Function:0 * [0 - 65535 ] View the Control word sent from thefrequency converter via the serial communi-cation port in hex code.16-01 Reference [Unit]Range: Function:0.000 Reference-FeedbackUnit*[-999999.000 -999999.000ReferenceFeed-backUnit]View the presentreference value appliedon impulse or analogbasis in the unitresulting from theconfiguration selectedin 1-00 ConfigurationMode (Hz, Nm or RPM).16-02 Reference [%]Range: Function:0.0 %* [-200.0 -200.0 %]View the total reference. The totalreference is the sum of digital, analog,preset, bus, and freeze references, pluscatch-up and slow-down.16-03 Status WordRange: Function:0 * [0 - 65535 ] View the Status word sent from the frequencyconverter via the serial communication port inhex code.16-05 Main Actual Value [%]Range: Function:0.00 %* [-100.00 - 100.00%]View the two-byte word sent withthe Status word to the bus Masterreporting the Main Actual Value.16-09 Custom ReadoutRange: Function:0.00 CustomRea-doutUnit*[-999999.99 -999999.99CustomRea-doutUnit]View the user-definedreadouts as defined in0-30 Custom Readout Unit,0-31 Custom Readout MinValue and 0-32 CustomReadout Max Value.3.16.1 16-1* Motor Status16-10 Power [kW]Range: Function:0.00kW*[0.00 -10000.00kW]Displays motor power in kW. The valueshown is calculated on the basis of theactual motor voltage and motor current.16-10 Power [kW]Range: Function:The value is filtered, and therefore approx.30ms may pass from when an input valuechanges to when the data read-out valueschange. The resolution of read-out valueon fieldbus is in 10 W steps.16-11 Power [hp]Range: Function:0.00hp*[0.00 -10000.00 hp]View the motor power in HP. The valueshown is calculated on the basis of theactual motor voltage and motor current.The value is filtered, and thereforeapproximately 30ms may pass fromwhen an input value changes to whenthe data read-out values change.16-12 Motor VoltageRange: Function:0.0 V* [0.0 - 6000.0 V] View the motor voltage, a calculatedvalue used for controlling the motor.16-13 FrequencyRange: Function:0.0 Hz* [0.0 - 6500.0 Hz] View the motor frequency, withoutresonance dampening.16-14 Motor CurrentRange: Function:0.00 A* [0.00 -10000.00 A]View the motor current measured as amean value, IRMS. The value is filtered,and thus approximately 30ms may passfrom when an input value changes towhen the data read-out values change.16-15 Frequency [%]Range: Function:0.00%*[-100.00 -100.00 %]View a two-byte word reporting theactual motor frequency (withoutresonance dampening) as a percentage(scale 0000-4000 Hex) of 4-19 Max OutputFrequency. Set 9-16 PCD Read Configu-ration index 1 to send it with the StatusWord instead of the MAV.Parameter Description VLT® HVAC Drive Programming GuideMG.11.CC.02 - VLT® is a registered Danfoss trademark 1193 3