EnclosuresizeDrive type IL [A] Fuse(gG/gL) [A]Mains, motor andbrake resistor cable Cu(1) [mm2]Mains terminal [mm2] Grounding terminal[mm2]FR7 0075 20072 5757280 3*25+16 2.5–50 Cu6–50 Al6–700088 20087 58887100 3*35+16 2.5–50 Cu6–50 Al6–700114 20105 5114105125 3*50+25 2.5–50 Cu6–50 Al6–70FR8 0140 20140 5140 160 3*70+35 25–95 Cu/Al 6–950170 20168 5168 200 3*95+50 95–185 Cu/Al 6–950205 20205 5205 250 3*150+70 95–185 Cu/Al 6–95FR9 0261 20261 5261 315 3*185+95 or2*(3*120+70)95–185 Cu/Al 6–950300 20300 5300 315 2*(3*120+70) 95–185 Cu/Al 6–951 Uses a correction factor 0.712.3.3 Cable and Fuse Sizes for 208–240 V and 380–500 V, FR4 to FR9, North AmericaTable 35: Cable and Fuse Sizes for VACON® NXS/NXP, North AmericaEnclo-sure sizeDrive type Fuse ClassFast Act-ing (T/J)[A]Mains, Motor, and brake re-sistor cable Cu [AWG] (1) (2)Mains terminal [AWG] Grounding terminal[AWG]FR4 0003 2—0008 20003 5—0007 510 3*16 AWG + 16 AWG 18 AWG - 4 AWG 18 AWG - 4 AWG0009 5 15 3*16 AWG + 16 AWG 18 AWG - 4 AWG 18 AWG - 4 AWG0011 2—0012 20012 515 3*14 AWG + 14 AWG 18 AWG - 4 AWG 18 AWG - 4 AWGSpecificationsOperating guide | VACON® NXS/NXP Air-cooledDPD00910G138 | Danfoss A/S © 2018.06