12.3.6 Cable and Fuse Sizes for 380–500 V, FR10 to FR11Table 38: Cable and Fuse Sizes for VACON® NXS/NXPEnclosuresizeDrive type IL [A] Fuse (gG/gL)[A]Mains, motor, and brake resistor cable(1) [mm2]Number ofsupply cablesNumber of mo-tor cablesFR10 0385 5 385 400 (3 pcs) Cu: 2*(3*120+70)Al: 2*(3*185Al+57CuEven/Odd Even/Odd0460 5 460 500 (3 pcs) Cu: 2*(3*150+70)Al: 2*(3*240Al+72Cu)Even/Odd Even/Odd0520 5 520 630 (3 pcs) Cu: 2*(3*185+95)Al: 2*(3*300Al+88Cu)Even/Odd Even/OddFR11 0590 5 590 315 (6 pcs) Cu: 2*(3*240+120)Al: 4*(3*120Al+41Cu)Even Even/Odd0650 5 650 400 (6 pcs) Cu: 4*(3*95+50)Al: 4*(3*150Al+41Cu)Even Even/Odd0730 5 730 400 (6 pcs) Cu: 4*(3*150+70)Al: 4*(3*185Al+57Cu)Even Even/Odd1 Uses a correction factor 0.712.3.7 Cable and Fuse Sizes for 380–500 V, FR10 to FR11, North AmericaTable 39: Cable and Fuse Sizes for VACON® NXS/NXP, North AmericaEnclo-sure sizeDrive type Fuse Class FastActing (T/J) [A]Mains, Motor, and brake resistor cable Cu [AWG] (1)(2)Number ofsupply ca-blesNumber ofmotor cablesFR10 0385 5 500 (3 pcs) Cu: 2*(3*250 kcmil + 2/0 AWG)Al: 2*(3*350 kcmil Al + 1/0 AWG Cu)Even/Odd Even/Odd0460 5 600 (3 pcs) Cu: 2*(3*300 kcmil + 2/0 AWG)Al: 2*(3*500 kcmil Al + 2/0 Cu AWG)Even/Odd Even/Odd0520 5 700 (3 pcs) Cu: 2*(3*350 kcmil + 3/0 AWG)Al: 2*(3*600 kcmil Al + 3/0 AWG Cu)Even/Odd Even/OddSpecificationsOperating guide | VACON® NXS/NXP Air-cooledDPD00910G142 | Danfoss A/S © 2018.06