Crusher jawMotor Full Load CurrentStart mode Constant currentStart ramp time 10 sCurrent limit 450%Excess start time 40 sLocked rotor time 30 sTable 7.10 Suggested Values for Crusher Jaw Applications7.2.3 LoggingsTo view performance information in real-time graphs, enterthe Loggings menu.• Current (%FLC).• Motor Temp (%).• Motor kW (%).• Motor kVA (%).• Motor pf.The newest information is shown at the right side of thescreen. The graph can be paused to analyze data bypressing and holding the [OK] key. To restart the graph,press and hold [OK].7.3 Main Menu[Main Menu] provides access to menus for setting up thesoft starter for advanced applications and for monitoringperformance.7.3.1 ParametersParameters allow viewing and changing all programmableparameters that control how the soft starter operates.To open Parameters, press [Main Menu] then selectParameters.Navigating through parameters• To scroll through parameter groups, press [▲] or[▼].• To view the parameters in a group, press [OK].• To return to the previous level, press [Back].• To close Parameters, press the [Back].Changing a parameter value• Scroll to the appropriate parameter and press[OK] to enter edit mode.• To alter the parameter setting, press [▲] and [▼].• To save changes, press [OK]. The setting shownon the display is saved and the LCP returns to theparameter list.• To cancel changes, press [Back]. The LCP returnsto the parameter list without saving changes.7.3.2 Parameter ShortcutThe VLT® Soft Starter MCD 500 also includes a parametershortcut, which gives direct access to a parameter withinthe Parameters menu.• To access the parameter shortcut, press [MainMenu] for 3 s.• Press [▲] or [▼] to select the parameter group.• Press [OK] or [Back] to move the cursor.• Press [▲] or [▼] to select the parameter number.Parameter shortcutPlease enter aparameter number01-01Programming VLT® Soft Starter MCD 50058 Danfoss A/S © 05/2016 All rights reserved. MG17K60277