14 Site PreparationCabinet PlacementThe cabinet must meet the following criteria:• Minimum cabinet size and airflow are according to the EIA standard.• Minimum of 5 inches (12.7 cm) between the side intake and exhaust vents and the cabinet wall.Rack MountingWhen you prepare your equipment rack, ensure that the rack is earth ground. The equipment rack must begrounded to the same ground point used by the power service in your area. The ground path must bepermanent.Fans and AirflowVentilation is side-to-side, with six fans on the left side of the switch that operate at a constant speed. Forproper ventilation, position the S25P chassis in an equipment rack (or cabinet) with a minimum of fiveinches (12.7 cm) of clearance around the side intake and exhaust vents. When two S25P systems areinstalled side by side, position the two S25P chassis at least 5 inches (12.7 cm) apart to permit properairflow. The acceptable ambient temperature ranges are listed in Environmental Parameters on page 33.As listed in Table 4, “Status Panel LED Display,” on page 12, the front panel of the S25P has an Alarmstatus LED, which is green when the switch is operating within required temperature parameters and allcomponents are operating normally, including fans. The LED is amber when the temperature orcomponents are outside expected parameters, red in a major alarm.SFTOS logs a temperature warning message when a temperature of 77 degrees C is reached, and logsanother message when the temperature returns to normal. The Command Line Interface (CLI) also reportsan alarm.Use the show logging command to see the log messages. For details, see the System Logs chapters of theSFTOS Command Reference and SFTOS Configuration Guide.In a stack, each unit has its own temperature monitoring and control. Status logging is identified by unit inthe system log.Fan replacement in the field is not offered as an option.