Table 19. Relative humidity specificationsRelative humidity SpecificationsStorage 5% to 95% RH with 33°C (91°F) maximum dew point.Atmosphere must be non-condensing at all times.Operating 10% to 80% relative humidity with 29°C (84.2°F) maximumdew point.Table 20. Maximum vibration specificationsMaximum vibration SpecificationsOperating 0.26 Grms at 5 Hz to 350 Hz (all operation orientations).Storage 1.88 Grms at 10 Hz to 500 Hz for 15 min (all six sidestested).Table 21. Maximum shock specificationsMaximum vibration SpecificationsOperating Six consecutively executed shock pulses in the positiveand negative x, y, and z axes of 40 G for up to 2.3 ms.Storage Six consecutively executed shock pulses in the positiveand negative x, y, and z axes (one pulse on each side ofthe system) of 71 G for up to 2 ms.Table 22. Maximum altitude specificationsMaximum altitude SpecificationsOperating 3048 m (10,000 ft)Storage 12,000 m (39,370 ft)Table 23. Operating temperature de-rating specificationsOperating temperature de-rating SpecificationsUp to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547ft) above 950 m (3,117 ft).35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319ft) above 950 m (3,117 ft).40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228ft) above 950 m (3,117 ft).Particulate and gaseous contamination specificationsThe following table defines the limitations that help avoid any equipment damage or failure fromparticulates and gaseous contamination. If the levels of particulates or gaseous pollution exceed thespecified limitations and result in equipment damage or failure, you may need to rectify the41