DVP02 T K-S / D VP 02 TU - S Te mp er ature C on tr ol Mod ul e M an ua l1 - 1 0_1 Mounting Arrangements and Wiring NotesPlease install PLC in an enclosure with sufficient space around it to allow heat dissipation as shown in the figure.DVPMPDDDDD > 50 mmWarning: shock hazard. Only for mounting in a rack or enclosure fully enclosing all live parts.Avertissement : risque d’électrocution. Ne doit être installé que dans un bâti ou un boîtier recouvrant entièrement toutesles pièces sous tension.1.5 Wiring Diagram22-16AWG< 1.5mm1. Use 22-16AWG (1.5mm) single or multiple core wire on I/O wiring terminals. The specification of the terminal isshown in the figure above. The PLC terminal screws shall be tightened to 1.95 kg-cm (1.7 in-lbs).2. DO NOT place the I/O signal wires and power supply wire in the same wiring duct.3. Warning: use conductors with insulation rated for at least 75 °cAvertissement : employer des conducteurs pour au moins 75 °c.4. For use with copper conductors only (excluding thermocouplers).destiné à être utilisé avec des conducteurs en cuivre seulement (sauf thermocouples).How to install DIN railDVP-PLC can be secured to a cabinet by using the DIN rail of 35mm in height and7.5mm in depth. When mounting PLC to DIN rail, be sure to use the end bracket tostop any side-to-side movement of PLC and reduce the chance of wires beingloosen. A small retaining clip is at the bottom of PLC. To secure PLC to DIN rail,place the clip onto the rail and gently push it up. To remove it, pull the retaining clipdown and gently remove PLC from DIN rail, as shown in the figure. PreviousNext |