D VP02 T K-S/D VP02 TU- S T emper ature C on tr ol Mod ule Man ua l2 - 2 2_2SVONOFF PVDead bandCooli ngCooling sensitiv ityadj ustmentHeatingH eating sensitiv ityadjus tm ent2.5 PID Control ModeWhen the PV is in the range of ERR_DBW, the PLC will run the PID operation according to the E value. When the PV isover the SV, the cross status will be established and the E value will be seen as 0 while running the PID operation untilthe PV goes over the range of ERR_DBW. If PID_DE is True, the PLC will run the derivative of PV. When the crossstatus is established, the Delta PV will be seen as 0 while running the derivative of PID operation. As the example shownbelow, the PLC will run the PID operation in the section A and will see the values of E and Delta PV as 0 while runningthe PID operation.PID Formula: Independent Formula & Derivative of E(PID_EQ=False & PID_DE=False) Independent Formula & Derivative of PV(PID_EQ=False & PID_DE=Ture)