Page 2 I.B. 3A74792H08Effective 0 9 / 2 0 14THE CIRCUIT BREAKERS DESCRIBED IN THISBOOK ARE DESIGNED AND TESTED TO OPERATEWITHIN THEIR NAMEPLATE RATINGS. OPERATIONOUTSIDE OF THESE RATINGS MAY CAUSE THEWARNING EQUIPMENT TO FAIL, RESULTING IN DEATH,BODILY INJURY AND PROPERTY DAMAGE.ALL SAFETY CODES, SAFETY STANDARDS AND/ORREGULATIONS AS THEY MAY BE APPLIED TO THISTYPE OF EQUIPMENT MUST BE STRICTLYADHERED TO.1-3 TYPE VCP-W AND VCP-WC VACUUM CIRCUIT BREAKER RATINGS (TABLES 1.1 AND 1.2)Table 1.1 Type VCP-W Ratings on Symmetrical Current Rating Basis Identification Rated ValuesT ►ABLECONTINUEDFROMNEXTPAGE ►CircuitBreakerTypeVoltage Insulation Level CurrentNominalVoltageClassMaximumVoltageVVoltageRangeFactorKV/KWithstand TestContinuousCurrentat 60 HzShort Circuit CurrentPowerFrequency(1 Minute)LightningImpulse1 .2x50 μsSym.Inter-ruptingat V(Isc)% dcCom-ponent(Idc)Asym.FactorS(ref.)Asym.Inter-rupting(I t )Max. Sym.Inter-ruptingat V/K(KxIsc)Max. Asym.Inter-ruptingat V/K(SxKxIsc)ClosingandLatchingCapabilityMomentaryCurrentWithstandCapabilityShortTimeCurrentDurationofShortTimeCurrentkV rms kV rms kV rms kV rms kV Peak Amperes rms kA rms %kA rmsTotal kA rmskA rmsTotal kA PeakkA rmsTotal kA rms s380 VCP-W 16and380 VCP-WR 1634.5 38 1 38 80 17060012001600200016 47 1.2 19.2 16 19.3 43 26 16 3380 VCP-W 25and380 VCP-WR 2534.5 38 1 38 80 17060012001600200025 47 1.2 30.0 25 30.0 68 40 25 3380 VCP-W 32and380 VCP-WR 3234.5 38 1 38 80 1706001200160020003000FC31.5 47 1.2 37.8 31.5 37.8 85 50 31.5 32500380 VCP-W 21and380 VCP-WR 2134.5 38 1.652380 170120020003000FC 21 47 1.2 39.5 3542.0 95 56 35 32500380 VCP-W 40and380 VCP-WR 4034.5 38 1 38 80 170120020003000FC250040 47 1.2 48.0 40 48.0 107 63 40 3 KEMA tested to applicable standards ANSI C37.04 - 1979, C37.09 - 1979, C37.06 - 1997 (operating Duty Sequence CO - 15s - CO). Typical operating time values: opening 45 ms, closing 75 ms, and reclosing 300 ms(18 cycles). K=1 .0, therefore E=E/K and I=KI, refer to the Consulting Application Catalog for further information. Rated and Tested also for Rapid Re-closing Capability O - 0.3s - CO. Not rated for Rapid Re-closing. At 23kV rms (Rated Max Voltage/K), Rated maximum symmetrical interrupting capability = 35kA rms (K x I). For Force Air Cooled Fixed Breaker Applications, consult Eaton.The ANSI C37.06 Standard requires 150kV BIL. If higher BIL levels are required, please refer to the “C” breakers. If you require 50 ms (3 cycle) interrupting time, please refer to the “C” breakers.The Standard Breaker is not rated for capacitor switching. If you require capacitor switching, please refer to the “C” breakers.