Page 13620-00082-01-us (en)ENGLISH2. PresentationDescription Available settings Default settingsIn/Out settingsLoad segments- Auto shutdowndelay[Disable] [0s] [1 s] [2 s]…[65354 s]During a power outage,authorizes UPS to turn off power toequipment connected to Group 1and/or Group 2 outlets.This feature allows the shedding ofnon-critical loads in order to conservebattery power for critical loadsconnected to the Primary group.Group 1: DisableGroup 2: DisableOverloadprealarm[10 %] [15 %] [20 %] ... [100 %] [105 %]Sets critical percentage of load wherealarm overload alarm occurs.[105 %]ON/OFF settingsCold start [Disable] [Enable]Enables the product to be started onbattery power.First cold start isw always disabled.EnableForced reboot [Disable] [Enable]If mains recover during a shutdownsequence:- if enabled, shutdown sequence willcomplete and wait 10 seconds priorto restart- if disabled, shutdown sequence willnot complete and restart will occurimmediately.EnableAuto restart [Disable] [Enable]Enables the product to restartautomatically when mains recoversafter a complete battery discharge.EnableEnergy saving [Disable] [Enable]If enabled, UPS will shutdown after5 min. of back-up time, if no load isdetected on the output.DisableSleep mode [Disable] [Enable]If disabled, LCD and communicationwill turn OFF immediately after UPSis OFF.If enabled, LCD and communicationstays ON 1h30 min after UPS is OFF.DisableRemote command [Disable] [Enable]If enabled, shutdown or restartcommands from software areauthorised.EnableRPO delay [0 s] [1s ] [2 s]...[180 s]Delays remote power off command[0 s]Battery settingsAutomatic batterytest[No test] [Every day] [Every week][Every month]Available only if battery charge modeis set to constant charge.Every week(in constant charge)otherwise following ABMLow batterywarning[1 %] [2 %] ... [100 %]The alarm triggers when the setpercentage of battery capacity isreached during a back-up time.20 %Restart batterylevel[1 %] [2 %] ... [100 %]If set, automatic restart will occuronly when percentage of batterycharge is reached.0 %Battery chargemode[ABM cycling] [Constant charge] ABM cyclingDeep dischargeprotection[Yes] [No]If set to Yes, the UPS automaticallyprevents battery from deep dischargeby adapting end of back-up timevoltage threshold.Yes