Page 26 620-00082-01-us (en)6. Appendices6.1 Technical specificationsTower 5P 850G 5P 1550GRack 5P 850G R 5P 1550G ROutput Power @ 230 V 850 VA600 W1550 VA1100 WOutput Power capacity@ 208 V765 VA540 W1395 VA990 WOutput Power @ 200 V 765 VA540 W1395 VA990 WAC Input power• Rated input voltage• Input voltage range• Input frequency rangeSingle phase 200-240 V160 to 294 V (1)47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system) (2)Output on battery power• Voltage• Frequency200/208/220/230/240 V (-10/+6 %) (3)50/60 Hz ±0.1 HzBattery(sealed lead acid,maintenance free)• StandardTower2 x 12 V7 Ah3 x 12 V9 AhRack4 x 6 V9 Ah6 x 6 V9 AhEnvironment• Operatingtemperature range• Storagetemperature range• Relative humidity• Noise level0 to 35 °C 0 to 40 °C-15 to +50 °C20 to 90 % (without condensation)< 40 dBA(1) The high and low thresholds can be adjusted using UPS settings.(2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).(3) Adjustable to 200/208/220/230/240 V, must be set to the identical AC power source value.When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,250 V which is IEC/EN 60898-1 standard compliant;When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A,250 V.This product is designed for IT power distribution system.FilterTransformer"AVR" Charger InverterBattery