Page 25620-00082-01-us (en)ENGLISH6. Appendices6.1 Technical specificationsTower 5P 750 5P 1000 5P 1500Rack 5P 550 R 5P 750 R 5P 1000 R 5P 1500 ROutput Power @ 120 V 550 VA420 W750 VA600 W1000 VA770 W1440 VA1100 WOutput Power capacity@ 125 V550 VA420 W750 VA600 W1000 VA770 W1440 VA1100 WOutput Power @ 100 V 458 VA350 W625 VA500 W833 VA641 W1080 VA825 WAC Input power• Rated input voltage• Input voltage range• Input frequency rangeSingle phase 100-125 V80 to 162 V (1)47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system) (2)Output on battery power• Voltage• Frequency100/120 V (-10/+6 %) (3)50/60 Hz ±0.1 HzBattery(sealed lead acid,maintenance free)• StandardTower2 x 12 V7 Ah2 x 12 V9 Ah3 x 12 V9 AhRack2 x 6 V9 Ah4 x 6 V7 Ah4 x 6 V9 Ah6 x 6 V9 AhEnvironment• Operatingtemperature range• Storagetemperature range• Relative humidity• Noise level0 to 35 °C 0 to 40 °C-15 to +50 °C0 to 90 % (without condensation)< 40 dBA(1) The high and low thresholds can be adjusted using UPS settings.(2) Up to 40 Hz in low -sensitivity mode (programmable using UPS settings).(3) Adjustable to 100/120/125 V, must be set to the identical AC power source value.For 5P Models - "CAUTION - To reduce the risk of fire, connect only to a circuit provided with 20 amperesmaximum branch circuit overcurrent protection in accordance with the National Electric Code,ANSI/NFPA 70".This product is designed for IT power distribution system.FilterTransformer"AVR" Charger InverterBattery