INSTALLATIONEaton® 9140 (9910-E82/E83) UPS Installation Guide for IBM® Applications 164201715 Rev 2www.eaton.com/ibm373. To change the factory-set defaults, see “User Settings” onpage 44.4. Turn the UPS on by selecting MENU from the system statusscreen, then select CONTROL, OUTPUT CONTROL, UPS TOONLINE, and OK to confirm.The indicator illuminates solid. The UPS is now in Normal modeand supplying power to your equipment.If the alarm beeps or a UPS alarm indicator stays on, see“Troubleshooting” in the Eaton 9140 UPS (7.5–10 kVA) User'sGuide on the User's Guide CD.5. If you installed an optional REPO or ROO, test the REPO or ROOfunction:Activate the external REPO or ROO switch. Verify the statuschange on the UPS display.Deactivate the external REPO or ROO switch and restart the UPS.6. If optional EBMs are installed, continue to “Configuring the UPS forEBMs” on page 52.NOTE The batteries charge to 80% capacity in less than 5 hours. However, it isrecommended that the batteries charge for 48 hours after installation or long-term storage.If you have questions about implementing non- or dual-redundant power,the following options are available: View the circuit diagrams at www.eaton.com/ibm and selectProducts > 9910 UPS for System i > E82/E83 > Product Literature Submit your question to “Ask the Expert” at www.eaton.com/ibm Submit your question to our FAQ database at www.eaton.com/ibmand select General Knowledge > Frequently Asked Questions Contact the IBM office or Business Partner servicing your account