OPERATIONEaton® 9140 (9910-E82/E83) UPS Installation Guide for IBM® Applications 164201715 Rev 2www.eaton.com/ibm45Table 10. User Settings (continued)Default SettingAvailable SettingsDescriptionLanguage Select Language: EnglishXCP Load Control [Enabled][Disabled] EnabledUpper Bypass V +0 through +20% (1% increments) +20%Lower Bypass V -0 through -20% (1% increments) -20%Bypass Freq Dev(Bypass Frequency Deviation Limits)1 through 5 Hz (1 Hz increments)NOTE This value sets the limits from 1 Hz to5 Hz of the nominal output configuration.3 HzQualify Bypass [Enabled][Disabled]NOTE This setting enables or disables thebypass qualification rules. When set toDisabled, Bypass is always available.EnabledAllow Bypass [Enabled][Disabled] EnabledSet Baud Rate Port 1 (RS232): [19200] [9600] [2400] [1200]Port 2 (SERVICE): [19200] [9600] [2400] [1200]9600Set Site (Wiring) Fault [Enabled][Disabled] DisabledContact Config* Contact Usage: [REPO][ROO][Disabled]Contact Type: [N/O][N/C]REPON/OFrequency Converter Mode [Enabled][Disabled]NOTE If bypass input fails while operating onsecond feeder input and neither utilityfrequency nor bypass frequency is availableto sync with, the UPS operates with differentfrequencies for output and input. When thissetting is Enabled, the UPS operates at a 50%derating to continue to meet operatingspecifications. When set to to Disabled, theUPS operates with no load derating.Enabled* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise,the changes do not take effect.