Eaton 9PX Lithium-Ion P-164001006—Rev 01 7The following table describes the status information provided by the UPSNote: If other indicator appears, see the troubleshooting for additional information.Table 4. LCD Operating StatusOperation status Cause DescriptionStandby mode The UPS is Off, waiting for startupcommand from user. Equipment is not powered untilbutton is pressed.Online mode The UPS is operating normally. The UPS is powering and protecting theequipment.Battery mode A utility failure has occured and the UPSis on Battery mode.The UPS is powering the equipment withthe battery power. Prepare yourequipment for shutdown.End of backup time The UPS is on Battery mode and thebattery is running low.Low Battery Warning settings:[Capacity] [0%] ... [100%][Runtime] [0mn] ... [60mn]The alarm triggers when the setpercentage of battery capacity orremaining back-up time is reached.High Efficiency mode The UPS is operating on High Efficiencymode.The UPS is powering and protecting theequipmentBypass mode An overload or a fault has occurred, or acommand has been received, and theUPS is in Bypass mode.Equipment is powered but not protectedby the UPS.22..66 DDiissppllaayy FFuunnccttiioonnssPress the ( ) button to activate the menu options. use the two middle buttons ( and ) to scroll throughthe menu structure. Press the ( ) button to select an option. Press the ESC button to cancel or return to theprevious menu.Table 5. Display FunctionsMain menu Submenu Display information or Menu functionMeasurements [Load] W VA A pf / [Input/Output] V Hz /[Efficiency] % / [Battery] % min V n°EBM / [Battery remaining life] months /[Average power usage] Wh / [Cumulatedpower] Wh / BMS InformationControl Go to Bypass Transfers the UPS on Bypass modeDisplay Functions