Eaton 9PX Lithium-Ion P-164001006—Rev 01 25RPO connections:RPO CommentsConnector type Terminal, 14 AWG maximum wiresExternal breaker specification 60 V DC/30V AC 20mA maxRPO11ROORemote On/Off (ROO)• Remote On/Off allows remote action of button to switch On/Off the UPS.• When contact changes from open to closed, the UPS is switched-on (or stays On).• When contact changes from closed to open, the UPS is switched-off (or stays Off).• On/Off control via button has priority over the remote control.RPO CommentsConnector type Terminal, 14 AWG maximum wiresExternal breaker specification 60 V DC/30V AC 20mA maxRPO11ROORemote Control Connection and Test1. Check the UPS is shut down and the electrical supply network disconnected.2. Remove RPO connector from the UPS by unfitting the screws.3. Connect a normally closed volt-free contact between the two pins of connector.RPO11Normally ClosedContact open: shut down of UPSTo return to normal operation, deactivate the external remoteshut downcontact and restart the UPS from the front panel.4. Plug the RPO connector into the back of the UPS and fix the screws.5. Connect and restart the UPS according to the previously described procedures.UPS Remote Control Functions