100 INSTALLATION AND OPERATION MANUAL 25-16327-B November 2020 www.eaton.comSection 4: AppendixMicro input module wiring (MCIM)Installation1 Fit the box in position using the mounting details below2 Connect the unit according to the diagram below3 Recommended Loop Cable Type: FIRETUF, FP200, MICCote:NNo addressing of the interface is required See control panel operation for detailsThere are no serviceable parts so no maintenance procedures applyStandard connectionsote:N1 Only connect cable screen to its adjacent earth terminal2 The end of line resistor provided must always be fitted, even if the input is unused3 Monitored inputs can detect open or short circuit faultsIN +EarthLoop In+Loop In-EarthLoop Out+Loop Out-IN -EARTHINPUTLOOPMCIM