15INSTALLATION AND OPERATION MANUAL 25-16327-B November 2020 www.eaton.comSection 1: System installation and designTechnical specificationPower specificationMains Fuse : 1 6A Slow BlowNominal Voltage : 230 Vac + 10%, -15%Nominal Current : 75mAThe Panel is protected by an internal thermal device, this requires no maintenanceBatteriesNumber of Batteries : 2Manufacturer: : YSP12-7Capacity : 7 AhBattery Fuse : 4A Quick Blow (F4)Maximum battery current; : 3 5 AmpsInputsAddressable LoopsMax Number : 1 or 2 (Panel depending)Max Loop Load per loop : 350 mAMax Number of Addressable : 200Devices per loopClass Change : Operated by external volt free contactOutputsConventional sounder circuitsNumber of sounder circuits : 2Total sounder Load : 1 5 AmpSounder Circuit Fuses (F1/2) : 1 6 Amp (Quick Blow)End of line device : 210Ω + DiodeAUX 1Max Load : 1 AmpFused (PTC2) : 1 1A polyswitch