14INM F892 Rev 1Specific Conditions of Safe Use:1. The apparatus is to be installed in an enclosure which maintains a minimum ingressprotection rating of IP54 and meets the enclosure requirements of EN 60079-0 and EN60079-15 as appropriate for the installation.9 3 Inspection and maintenancea) Inspection and maintenance should be carried out in accordance with European,national and local regulations which may refer to the standard EN 60079-17. Inaddition specific industries or end users may have specific requirements whichshould also be met.b) Access to the internal circuitry must not be made during operation.9 4 RepairThis product cannot be repaired by the user and must be replaced with an equivalentcertified product.9 5 MarkingEach device is marked in compliance with the Directive/Regulation. This informationapplies to products manufactured during or after the year 2007.Typical certification markingsF801 : F802 :-40CK 0715Made in the UKRelcom Inc.II 3 G Ex nA IIC T4 GcForest Grove, OR 97116 USACl I Div 2 ABCD T4Cl I Zone 2 IIC T4Install per 502-086RELC07ATEX1002XInput: 30VDC, 4.5A maxOuput: 24VDC, 420mA max/segRELC21UKEX1014XN 0812-40C 60% Load)-40CMade in the UKRelcom Inc.II 3 G Ex nA IIC T4 GcForest Grove, OR 97116 USACl I Div 2 ABCD T4Cl I Zone 2 IIC T4Install per 502-086RELC07ATEX1002XRELC21UKEX1014XInput: 30VDC, 7A maxOuput: 30VDC, 580mA max/segF8xx Carrier :Relcom Inc.Made in the USA-40C0715Cl I Div 2 ABCD T4Cl I Zone 2 IIC T4Install per 502-087Relcom Inc.II 3 G Ex nA IIC T4 GcRELC07ATEX1002XRELC21UKEX1014XInput: 30VDC, 8.5A maxOutputs: see Modules