Effective July 2010Instructional Leaflet IL8700C39-04OPTIM OPTIMDIGITRIP RMS Type 510 610 810 910 750 1050Instruction Leaflet No. I.L. 29-885 I.L. 29-886 I.L. 29-888 I.L. 29-889 I.L. 29C891 I.L. 29C891Long Delay Setting X X X X X XLong Delay Time X X X X X XLong Time Slope (I2t - I4t) X XLong Time Memory Powered X X X X X XOvertemperature X X X X X XShort Delay Pick-up OPT. OPT. OPT. OPT. X XShort Delay Time OPT. OPT. OPT. OPT. X XFlat/I2T Response X X X X X XZone Interlocking j j j j j jInstantaneous Pick-up OPT. OPT. OPT. OPT. X XDIScriminator Disable s s s s X XGround Fault Pick-up OPT. OPT. OPT. OPT. OPT. OPT.Ground Fault Time OPT. OPT. OPT. OPT. OPT. OPT.Flat/I2t Response X X X X X XGround Time Memory X X X X X XZone Interlocking j j j j j jGround Fault Alarm Only OPT. OPT.Interchangeable Rating Plug X X X X X XAuto Lockout After Trip X X X X XMode of Trip LEDs X X X X X XBattery - for Mode of Trip LEDs X X X X X XBattery Status LED (Green) X X X X X XBattery Test Pushbutton X X X X X XPower/Relay Module X X X X XRemote Signal ContactHigh Load Alarm X X X X XLong Delay Trip X X X X XShort Circuit Trip X X X X XGround Fault Trip o o o o oGround AlarmIntegral Test Provisions X X X XTrip Unit Status Indication LED X X X X X XDisplay Message Test l l4 Digit Display X X XIA Current X X XIB Current X X XIC Current X X XIG Ground o o oDisplay Stepping Pushbutton X X XTotal Harmonic Distortion [THD] LED XPer Harmonic XWaveform Capture m m4 Digit DisplayPhase to Phase [VAB] LED XPhase to Phase [VBC] LED XPhase to Phase [VCA] LED XProtectionVoltageMeteringHarmonicCurrentCurrent Metering(Local and Remote) Test Remote Signals Local TripIndicatorsX = Standard j Use of zone interlocking is optional with breaker wiring modification.OPT = Optional k Remote location only unless optional AEM local monitor is used.l Local on face of trip unit. Remote via INCOM/IMPACC to AEM1 or AEM2 or direct to host computer.m Remote only - direct to host computer via INCOM/IMPACC.n On AEM denoted by absence of response from addressed breaker.o Supplied only when trip unit is equipped with ground fault protection option.p Requires spring release or electrical operator option.7eaTOn CORPORaTIOn www.eaton.comTable 1 Digitrip Trip Unit Characteristics