8Instruction Leaflet IL29C204I Installation Instructions for Motor Operator for3- and 4-Pole ND, NB, NC, MD, MA, MC TypeCircuit Breakers and Molded Case SwitchesEATON CORPORATION www.eaton.comFrequency (Hz)Motor-inR ushCurrent (A)Catalog NumberTable 1-1. Available Motor Operator Ratings and Operating Conditions50/60 50/60 Dc Dc Dc15 13 50Catalog NumberMotor-in -RushCurrent (A)Style Number15Rated Voltage 120 (110) 208 240 (220) 125 VdcStyle NumberRated Voltage 120 208 240 480 125 Vdc 24 VdcFrequency (Hz) IOperator is an intermittent duty device. The safe duty cycle (OFF to ON to OFF) should not exceed one per minute.Electrical Operating times at rated voltage.a. To turn breaker ON - 0.2 second (12 cycles) max.b. To turn breaker OFF - 0.2 second (12 cycles) max.Motor Operating temperature; Class ā A temperature limits apply.Applied Voltage should be no less than 85% or no more than 110% of rated voltage.Operator applications on supply of 480 Vac utilizes a transformer. (Customer Supplied)EOP5T07 EOP5T09 EOP5T11 EOP5T15 EOP5T26 EOP5T22 EOP5T2124 Vdc19 15 45519 13 15 50480/115 Vac1484D60G01 1484D60G02 1484D60G03 1484D60G04 1484D60G05 148460G08 1484D60G031484D60G31 1484D60G32 1484D60G33 1484D60G34 1484D60G35 1484D60G36