166.2 Special regulations for ESF-E30/13 without optional Wall MountingMANUAL ESF-E30 40071860041 (G) November 2018 www.ceag.de6.2 Special regulations for ESF-E30/13without optional Wall MountingAlignmentThe enclosures must be screwed to the masonry withdowels which have a general building approval. Thestatic conditions must be taken into account. The screwconnection must not cause any stresses to be applied tothe housing. It must be ensured that the installation orattachment of the electrical distributors does not impairthe stability, sound insulation and fire resistance of theadjacent component - even in the event of fire.The approval object of type “US-S ESF30 13-S” must besuspended from solid walls (d ≥ 240 mm) with a fire resis-tance duration of at least 30 minutes. The approval objectof type “US-S ESF30 28-S” must be placed vertically onsolid walls (d ≥ 240 mm) and on solid ceilings (d ≥ 150mm) made of non-combustible building materials with afire resistance duration of at least 30 minutes. Assignmentof the classified fire behaviour properties to the buildingauthority requirements in accordance with Building Regu-lations List A Part 1 Annex 0.2.1 or 0.2.2 (in the respec-tively valid edition, see www.dibt.de).Interior wall-mounting bywall-mounting-holes.Cable seizureThe cables have to meetcircuit integrity which isrequired on-site.Put the cable sheatsthrough the cable coolingroom and insert the cablecores into the electricaloperating room by usingthe second separation.Cablecooling roomElectricaloperation roomWallmountingDetal XScrew connectionFor mounting the distributor housing to adjacent solidconstruction components, dowels (at least M8) and steelscrews must be used that are suitable for this purposeand that comply to the static requirements and generalconstructional or European technical approvals. The specialrequirements of specific general constructional approvalsor European technical approvals must be observed. Moun-ting of the electrical distributors to adjacent solid const-ructional components must be implemented via factory-processed mounting facilities – holes in the rear wall onthe inner of the distributor housing. The screw connectionmust not subject the enclosure to any tension.Insertion of cables in the enclosureIt must be ensured that cables with circuit integrity areinserted in the enclosure vertically and without tension.Depending on the cable equipment, the general appraisalcertificate (allgemeines bauaufsichtliches Prüfzeugnis,ABP) or general technical approval (allgemeine bauauf-sichtliche Zulassung, ABZ) of the relevant manufacturermust be observed outside the enclosure.