LOAD8 Amp resistive and incandescent lighting6 Amp fluorescent lighting3 Amp compact fluorescent lighting3 Amp low energy lighting3 Amp low voltage lighting (switch primary of transformer)Fluorescent lighting (max 6 fittings recommended)For fluorescent lighting total power factor correction ca-pacitance must not exceed 40μF.3 Amp fans and ventilation equipmentSwitch SON lighting loads via a contactorSUPPLY VOLTAGE 220-240 Volts AC 50 HzTIME OUT PERIOD Adjustable 10s to 30mLIGHT LEVEL Light to darkTERMINAL CAPACITY 2.5 mm2MATERIAL Flame retardant ABSTYPE Class 2TEMPERATURE -10°C to 35°CCONFORMITY EMC-2014/30/EULVD-2014/35/EUPart NumbersSpecificationDetection PatternPPD-C-230V Ceiling mounted presencedetectorSB-C Surface mounting backboxSB-C-EX Surface mounting backbox extenderRef 9850-000578-00#WD859 Issue 2.0Eaton Lighting SystemsUsk House, LakesideLlantarnam Park,Cwmbran, NP44 3HD, UKTel: +44 (0)1633 838088Fax: +44 (0)1633 867880lightingcontrolsolutions@eaton.comwww.eatonlightingsystems.comIMPORTANT NOTICE!This device should be installed by a qualified electrician inaccordance with the latest edition of the IEE wiringregulations.Due to our policy of continual product improvement we reserve the right to alter thespecification of this product without prior notice.The PPD-C-230V series of presence detector switches are designed to provide automatic control oflighting, heating or ventilation loads. They detect movement using a PIR sensor and turn the load on.When an area is no longer occupied the load will switch off after an adjustable time out period.An adjustable internal light sensor provides additional energy saving in lighting applications. When anarea is occupied lighting is only switched on when the level of natural light is below a preset level.When the unit is first powered up the PIR sensor will always detect immediately regardless of whetherthe room is occupied.OverviewProduct GuidePPD-C-230VCeiling Presence Detector