WIRING1. Pull field wiring into cover module.2. Close all unused conduit entries with conduitplugs provided. To prevent galling and to ensurewater-tightness, lubricate conduit plugs withCrouse-Hinds HTL lubricant before installing, and securewrench-tight with at least five (5) full threads engaged(42-52 ft.-lb. for 3/4” plugs, and 58-68 ft.-lb. for 1” plugs).3. Hang LED luminaire on the cover module hinge hook.See Figure 2a.4. Connect supply wires to luminaire wire leads or terminalblock per the attached wiring diagrams using methodsthat comply with all applicable codes. See Figure 2b.Tighten all electrical connections.5. Close driver housing onto cover module, making surethat all wires are safelyinside driver housing.Tighten captive closingscrew to 30 in.-lbs. (3.4N-m). Ensure two (2)bosses on driver housingare in contact with covermodule.6. Turn power on.FIGURE 2aINSTALLATIONMOUNTING1. Mount the cover module in its support position.• Ceiling and wall mount: mark and drill desired locationon mounting surface. Secure with 1/4” (6mm) boltsor lag screws (not provided).• Pendant, stanchion mount: securely thread onto theappropriate NPT size conduit. Tighten set screwlocated in the conduit hub. See Figure 1.• Crouse-Hinds HTL thread lubricant must be added tothe conduit threads to prevent water from enteringthe fixture.IF 1628 • 05/22 Copyright © 2022, Eaton’s Crouse-Hinds Division Page 1Pro-Champ LED LuminairesPVM Series Industrial LED LightingInstallation & Maintenance InformationSAVE THESE INSTRUCTIONS FOR FUTURE REFERENCEIF 1628WARNINGTo avoid the risk of fire, explosion or electricshock, this product should be installed, inspectedand maintained by a qualified electrician only, inaccordance with all applicable electrical codes.WARNINGTo avoid electric shock:• Be certain electrical power is OFF before and duringinstallation and maintenance.• Luminaire must be supplied by a wiring system forthe specific hazardous locations suitable per localcode with an equipment grounding conductor.To avoid burning hands:• Make sure LEDs and drivers are cool to touch whenperforming maintenance.Set-screwOpenHingeGround WiresFIGURE 1APPLICATIONLuminaire construction is designed for use indoors andoutdoors in marine and wet locations, where moisture, dirt,corrosion, vibration, and rough usage may be present.• Wet location, Type 4X• UL1598 Luminaires, UL1598A Marine• IP66• cULFIGURE 2bIF 1628 • 05/22 Copyright © 2022, Eaton’s Crouse-Hinds Division Page 2PVM supplied with a choice of voltages:• 100-277VAC 50/60 Hz• 108-250VDC• 347V• 480VTRANSFORMERGROUND PELINEVOLTAGENCOM347/480 VL1GND (SEE NOTE 4 SHT 1)GRNGRNACL(BLK)ACN(WHT)GND (SEE NOTE 4 SHT 1)COM WHTBLKINPUTACN(WHT)ACL(BLK)GRNWHT190/270 V BLKINPUTDRIVER # 2 OUTPUTV-(BLK)V+(RED)V-(BLK)DRIVER # 1 OUTPUTV+(RED)GROUNDLINEVOLTAGEPENL1GNDGRNGRNACL(BLK)ACN(WHT)WHTBLKINPUTDRIVER V+(RED)OUTPUTV-(BLK) BLKREDDENOTES CONNECTIONCLOSED END CRIMP CONNECTORPER BOMDENOTES WIRE CROSSOVER, NOT CONNECTION POINTRED or PURPLEBLKBLKBLKREDBLKRED or PURPLE REDPVM9LPVM7LPVM5LPVM3LBLKREDPVM3LNPEL1BLKV-(BLK)ACN(WHT)WHTDRIVERGRN(GND)ACL(BLK)ACN(WHT)(GND)GRNWHTBLKGRNINPUTV+(RED)V-(BLK)OUTPUTRED or PURPLEBLKDRIVERACL(BLK)BLKINPUTV+(RED)OUTPUTRED or PURPLEBLKREDBLKPVMV9LPVM7LPVM5LREDGROUNDVOLTAGELINE5L, 7L & 9LWIRING DIAGRAM FOR:DIAGRAM #1:PVM3L SERIESWIRING DIAGRAM FOR:DIAGRAM #2:347 OR 480 VOLT TRANSFORMERWIRING DIAGRAM FOR:DIAGRAM #3:PECOMCOM190/270 V347/480 VTRANSFORMERACL(BLK)ACN(WHT)V+(GREY)OUTPUTV-(BLK)INPUTV-(BLK)V+(GREY)OUTPUTBLKBLKREDREDWHTBLK DRIVER # 2DRIVER # 1ACL(BLK)INPUTACN(WHT)BLKWHTLINEVOLTAGENPVM11LBLKGREYBLKGREYGROUNDL1GREYBLKACN(WHT)INPUTACL(BLK) DRIVER # 3BLKWHTV+(GREY)V-(BLK)OUTPUTGRNBLKRED347 OR 480 VOLT TRANSFORMERWIRING DIAGRAM FOR:DIAGRAM #4:ON PVM11LNOTE: Ground wire must be added to mounting plateground lug and to lugs on entry hubs. Ground wire included.Directive EU 2019/2022This product contains a light source of energy efficiencyclass D or E.WARNINGTo avoid explosion:• Make sure the supply voltage is the same as therated luminaire voltage.• Do not install where the marked operatingtemperatures exceed the ignition temperature of thehazardous atmosphere.• Do not operate in ambient temperatures above thoseindicated on the luminaire nameplate.• Use only replacement parts from Crouse-Hinds.• Use proper supply wiring as specified on theluminaire nameplate.• All surfaces must be clean.• Before opening wiring compartment, electrical powerto the luminaire must be turned off and area must befree from hazardous atmosphere. Keep tightly closedwhen in operation.• To minimize the risk from electrostatic discharge,when cleaning, wipe the lens with a clean, dampcloth.• LED compartment is non serviceable. Do not open.