Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual 164201687 Rev 4 www.eaton.com/powerquality 3-1Chapter 3 Installation Plan and UnpackingUse the following basic sequence of steps to install the UPS:1. Create an installation plan for the battery cabinet (Chapter 3).2. Prepare your site for the battery cabinet (Chapter 3).3. Inspect and unpack the battery cabinet (Chapter 3).4. Unload and install the battery cabinet, and wire the system (Chapter 4).5. Complete the Installation Checklist (Chapter 4).6. Have authorized service personnel perform preliminary operational checks andstartup.NOTE Startup and operational checks must be performed by an authorized Eaton Customer ServiceEngineer, or the warranty terms specified on page W-1 become void. This service is offered as part of thesales contract for the UPS. Contact service in advance (usually a two-week notice is required) to reserve apreferred startup date.3.1 Creating an Installation PlanBefore installing the battery cabinet, read and understand how this manual applies tothe system being installed. Use the procedures and illustrations in paragraph 3.2 andChapter 4 to create a logical plan for installing the system.3.2 Preparing the SiteFor the battery system to operate at peak efficiency, the installation site should meetthe environmental parameters outlined in this manual. If the UPS is to be operated atan altitude higher than 1500m (5000 ft), contact your service representative forimportant information about high altitude operation. The operating environment mustmeet the weight, clearance, and environmental requirements specified.3.2.1 Environmental and Installation ConsiderationsThe battery system installation must meet the listed guidelines. Failure to followguidelines may void your warranty. The system must be installed on a level floor suitable for computer or electronicequipment. If perforated floor tiles are required for ventilation, place them in front of thebattery cabinet. The system must be installed in a temperature and humidity controlled indoor areafree of conductive contaminants. The battery cabinet is to be installed in a standalone configuration. The recommended installation location for battery cabinets located adjacent to theUPS is on the right side of the UPS cabinet. This location will allow for futureexpansion using an external module.Figure