INSTALLATIONPower Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual 164201687 Rev 4 www.eaton.com/powerquality 4-3W A R N I N GRISK OF INSTABILITY. Turning the jacking bolts unevenly may cause the cabinet to become unbalanced. Toprevent tipping the cabinet, raise and lower the jacking bolts evenly.C A U T I O NCABINET MAY TIP. The battery cabinet should only be raised approximately 3 mm (1/8”) above the floor (justenough to allow removal of the 46 supports).7. Remove the hardware loosened in Step 5. Pull the 46 supports out from underthe battery cabinet. Discard or recycle them in a responsible manner.C A U T I O NCABINET MAY FALL. Do not loosen the hardware attaching the side or front supports to the cabinet base, orthe front and side supports to each other, at this time. The cabinet must be lowered by the jacking boltsbefore the supports can be removed.8. Carefully and evenly lower the cabinet by turning each jacking bolt consecutively twofull turns (maximum) until the casters contact the floor, and the cabinet is no longersupported by the jacking bolts.9. Remove the jacking bolts and discard or recycle them in a responsible manner.10. Remove the hardware holding the front, rear, and side supports to the cabinetbase. Discard or recycle the hardware and support brackets in a responsiblemanner.11. Roll the battery cabinet to its final location.12. Repeat Steps 3 through 11 for each cabinet you are preparing to install.4.3 Model 1085 or 1085HR Battery Cabinet InstallationThe 9395 Model 1085 or 1085HR battery cabinet is designed to be installed in astandalone configuration. Customer-supplied conduit and wiring is installed externallybetween each battery cabinet and the UPS or UPS disconnect. Battery cabinets maybe installed adjacent to the UPS or in a separate location.C A U T I O NThe 1085 and 1085HR battery cabinets CANNOT be intermixed. Serious damage to equipment may result.4.3.1 Mechanical InstallationUse this procedure to install the battery cabinet. The battery cabinet shown inFigure 4‐2 is located adjacent to the UPS cabinet, but may be located in a separatelocation.There are no battery cabinet‐to‐UPS mechanical attachment requirements for thistype of system. However, individual battery cabinets must be attached and groundedto each other, as described in this section.