Contents - important safety instructions
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Table Of Contents
- Introduction
- Figure 1‐1. Power Xpert 9395 Plus 1 UPS (225–275 kVA) Cabinet
- Control Panel
- Field Installed UPM
- Inherent Redundancy
- Variable Module Management System and High Alert Modes
- Battery System
- Symbols, Controls, and Indicators
- For More Information
- Safety Warnings
- UPS Installation Plan and Unpacking
- Installation Considerations
- Figure 3‐1. UPS Cabinet Dimensions (Front View)
- Figure 3‐3. UPS Cabinet Dimensions (Top View)
- Figure 3‐6. UPS Cabinet Center of Gravity
- UPS System Power Wiring Preparation
- UPS System Interface Wiring Preparation
- Distributed Bypass Power Wiring Preparation
- Inspecting and Unpacking the UPS Cabinet
- Figure 3‐8. Power Xpert 9395 Plus 1 UPS (225–275 kVA) Cabinet as Shipped on Pallet
- UPS System Installation
- Figure 4‐1. Removing the Left Side Shipping Bracket
- Figure 4‐2. Removing the Right Side Shipping Bracket
- Battery System Installation
- Hole Barrel Lug Terminations to Bus Bar Installation
- Figure 4‐4. Conduit and Wire Entry Locations
- Figure 4‐5. UPS Power Terminal Locations – Common Rectifier Feed
- Figure 4‐6. UPS Power Terminal Detail AA – Common Rectifier Feed
- Figure 4‐7. UPS Power Terminal Locations – Separate Rectifier Feed
- Figure 4‐8. UPS Power Terminal Detail AA – Separate Rectifier Feed
- Battery Power Wiring
- Figure 4‐10. UPS Power Terminal Detail BB – Common Battery
- Installing Interface Connections
- Figure 4‐12. Interface Terminal Locations
- Figure 4‐13. Interface Terminal Detail
- Figure 4‐15. Terminal Blocks TB1, TB2, and TB3 Connector Assignments
- TB1 Battery Interface Connections
- Figure 4‐16. Typical Battery Interface Connection
- X-Slot Connections
- Installing a REPO Switch
- Figure 4‐19. REPO Switch
- Figure 4‐20. Normally-Open REPO Switch Wiring
- Figure 4‐21. Normally‐Closed REPO Switch Wiring
- Installing Options and Accessories
- Installing an Optional Powerware Hot Sync CAN Bridge Card
- Figure 5‐2. Powerware Hot Sync CAN Bridge Card Connections
- Installing Distributed Bypass Control Wiring
- Figure 5‐3. Distributed Bypass System CAN and Pull-Chain Simplified Interface Wiring
- Figure 5‐5. Distributed Bypass Pull-Chain Wiring without MOBs
- Figure 5‐6. Distributed Bypass Pull-Chain Wiring with MOBs
- Installing an Optional Remote Monitor Panel II
- Figure 5‐7. Remote Monitor Panel II and Remote Monitor Panel II Terminal Locations
- Installing an Optional Relay Interface Module II
- Figure 5‐9. J1, J2, J3, and J4 15-Pin D-Sub Connectors
- Installing an Optional Supervisory Contact Module II
- Figure 5‐11. Supervisory Contact Module II TB2
- Accessory Mounting Dimensions
- Figure 5‐13. Relay Interface Module II Dimensions
- Figure 5‐14. Supervisory Contact Module II Dimensions
- Understanding UPS Operation
- Single UPS
- Energy Saver System Mode
- Harmonic Reduction System (HRS)
- Bypass Mode
- Battery Mode
- Single UPS System Oneline Configurations
- Figure 6‐5. UPS System – Common Rectifier Feed, Common Battery, Dual‐Feed Configuration
- Figure 6‐6. UPS System – Common Rectifier Feed, Separate Battery, Dual‐Feed Configuration
- Figure 6‐7. UPS System – Separate Rectifier Feed, Separate Battery, Dual‐Feed Configuration
- Figure 6‐8. Simplified Dual-Feed UPS with Maintenance Bypass Panel
- Multiple UPS Distributed Bypass System
- Online Mode – Distributed Bypass
- Bypass Mode – Distributed Bypass
- Figure 6‐10. Path of Current through the UPSs in Bypass Mode – Distributed Bypass
- Battery Mode – Distributed Bypass
- Multiple UPS Distributed Bypass System Oneline Configurations
- Figure 6‐12. Typical Distributed Bypass System (1+1 and 2+0 Configurations)
- Figure 6‐13. Typical Distributed Bypass System (2+1 and 3+0 Configurations)
- Figure 6‐14. Typical Distributed Bypass System (3+1 and 4+0 Configurations)
- UPS Operating Instructions
- Status Indicators
- Using the LCD and Pushbuttons
- Using the Menu
- Display Menu Operation
- Load Off Screen
- Figure 7‐6. Typical System Status Screen
- Single UPS Operation
- Enable Energy Saver System Mode from the UPS Command Menu
- Disable Energy Saver System Mode from the UPS Command Menu
- Enable Variable Module Management System Mode from the UPS Command Menu
- Start Variable Module Management System High Alert Mode from the UPS Command Menu
- Enable Energy Saver System Mode from the Bypass Command Menu
- Start Energy Saver System High Alert Mode from the Bypass Command Menu
- Disable Variable Module Management System Mode from the Bypass Command Menu
- Starting the UPMs
- Starting a Single UPM
- Transfer from Online to Bypass Mode
- Transfer from Bypass to Online Mode
- Single UPM Shutdown
- Single UPM Restart
- UPS and Critical Load Shutdown
- Using the UPS LOAD OFF Pushbutton or Command
- Using the Remote Emergency Power-off Switch
- Multiple UPS Distributed Bypass Operation
- Disable Energy Saver System Mode from the Bypass Command Menu
- Enable Variable Module Management System Mode from the Bypass Command Menu
- Start Variable Module Management System High Alert Mode from the Bypass Command Menu
- Transfer from Online to Bypass Mode and Shut Down UPMs
- Single UPS Shutdown using Load Off
- Single UPS Shutdown using UPM Shutdown
- Single UPS Restart
- Color Touchscreen Control Panel
- Using the Color Touchscreen Control Panel
- Figure 7‐12. Sign In or Password Request Screen
- Using the Main Menu Buttons
- Power Maps Screen (Online Mode)
- Figure 7‐16. Average Efficiency Screen from Home Screen
- Power Maps Screen (Bypass Mode)
- Meters Summary Screen
- Input Meters Screen
- Figure 7‐23. Output Meters Screen
- Input Meters Detail Screen
- Battery Meters Screens
- Figure 7‐28. Battery Log Detail
- System Events Main Screen
- Figure 7‐31. User Log Screen
- System Status Screen and Controls
- Figure 7‐35. Module Control Detail Screen
- Settings Screen
- Configuration Options Screen
- Figure 7‐41. Disable ESS Screen
- Statistics Basic Screen
- ESS Comparison Screen
- UPS Module Map Screen
- UPS Operation using the Color Touchscreen Control Panel
- Communication
- eNotify Service
- Power Management Software
- Remote Monitor Panel II
- Relay Interface Module II
- Supervisory Contact Module II
- UPS Maintenance
- Performing Preventive Maintenance
- PERIODIC Maintenance
- Recycling the Used Battery or UPS
- Product Specifications
- UPS Output
- Warranty
|
TABLE OF CONTENTSPower Xpert 9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual 164201710 Rev 7 www.eaton.com/powerquality iii7.2.8 System Status Screen and Controls 7-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.2.9 Load Off Screen 7-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3 Single UPS Operation 7-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.1 Starting the UPS in Online Mode 7-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.2 Enable Energy Saver System Mode from the UPS Command Menu 7-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.3 Disable Energy Saver System Mode from the UPS Command Menu 7-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.4 Start Energy Saver System High Alert Mode from the UPS Command Menu 7-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.5 Enable Variable Module Management System Mode from the UPS Command Menu 7-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.6 Disable Variable Module Management System Mode from the UPS Command Menu 7-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.7 Start Variable Module Management System High Alert Mode from the UPS Command Menu 7-17. . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.8 Starting the UPS in Bypass Mode 7-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.9 Enable Energy Saver System Mode from the Bypass Command Menu 7-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.10 Disable Energy Saver System Mode from the Bypass Command Menu 7-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.11 Start Energy Saver System High Alert Mode from the Bypass Command Menu 7-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.12 Enable Variable Module Management System Mode from the Bypass Command Menu 7-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.13 Disable Variable Module Management System Mode from the Bypass Command Menu 7-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.14 Start Variable Module Management System High Alert Mode from the Bypass Command Menu 7-20. . . . . . . . . . . . . . . . . . . . . . . . .7.3.15 Starting the UPMs 7-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.16 Starting a Single UPM 7-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.17 Transfer from Online to Bypass Mode 7-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.18 Transfer from Bypass to Online Mode 7-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.19 Transfer from Online to Bypass Mode and Shut Down UPMs 7-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.20 Single UPM Shutdown 7-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.21 Single UPM Restart 7-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.22 UPS and Critical Load Shutdown 7-27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.23 Charger Control 7-27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.24 Using the UPS LOAD OFF Pushbutton or Command 7-28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.3.25 Using the Remote Emergency Power-off Switch 7-30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4 Multiple UPS Distributed Bypass Operation 7-31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.1 Starting the Distributed Bypass System in Online Mode 7-31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.2 Enable Energy Saver System Mode from the UPS Command Menu 7-32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.3 Disable Energy Saver System Mode from the UPS Command Menu 7-33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.4 Start Energy Saver System High Alert Mode from the UPS Command Menu 7-33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.5 Enable Variable Module Management System Mode from the UPS Command Menu 7-34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.6 Disable Variable Module Management System Mode from the UPS Command Menu 7-34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.7 Start Variable Module Management System High Alert Mode from the UPS Command Menu 7-35. . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.8 Starting the Distributed Bypass System in Bypass Mode 7-35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.9 Enable Energy Saver System Mode from the Bypass Command Menu 7-36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.10 Disable Energy Saver System Mode from the Bypass Command Menu 7-37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.11 Start Energy Saver System High Alert Mode from the Bypass Command Menu 7-37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.12 Enable Variable Module Management System Mode from the Bypass Command Menu 7-38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.13 Disable Variable Module Management System Mode from the Bypass Command Menu 7-38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.14 Start Variable Module Management System High Alert Mode from the Bypass Command Menu 7-39. . . . . . . . . . . . . . . . . . . . . . . . .7.4.15 Starting the UPS UPMs 7-39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.16 Starting a Single UPM 7-41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.17 Transfer from Online to Bypass Mode 7-42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.18 Transfer from Bypass to Online Mode 7-42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.19 Transfer from Online to Bypass Mode and Shut Down UPMs 7-43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.20 Single UPM Shutdown 7-43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.21 Single UPM Restart 7-44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7.4.22 Single UPS Shutdown using Load Off 7-45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PreviousNext |