Page 108 IM02601004E www.eaton.com6 Meter Settings Using the Web ServerINTERNAL I/OInternal I/O is divided into two sub-categories: Inputs and Outputs. The arrow for each allowsyou to identify input or output and assign functionality to it.INTERNAL I/O - INPUTSThe Input section of the Internal I/O lists each of the 8 digital inputs, their IDs, and function. TheFunction assigned to the digital input dictates what or how the digital input responds, as a Coun-ter, calculating summation log trends, giving Status via e-mail or capturing Waveforms, etc. Input8 is fixed for real time pricing mode. Only one input can be selected for Demand Sync and DCF77 Time Sync, and only input 8 can be configured for Real Time Pricing.Locating Internal I/O Input Setup on the Web1. From the Settings main page, select the I/O tab.2. Select the Internal I/O arrow, then the Inputs arrow.3. Underneath the Inputs arrow are arrows for each of the 8 digital inputs. Within each digitalinput is a list displaying all of the current settings.4. Click Edit to change any of the listed settings.5. Click Save when new entries are completed. Click Close to exit Edit mode.Use the ID text box to name the digital input if desired. Use the Mode drop down box to selectthe function (Counter, Status, Demand Sync, DCF 77, and Disable) of each digital input. Ad-ditional information may be required for some functions. For example, if Counter is selected,Pulse Weight, Pulse Multiplier, and Units must be entered. If Status is selected, the Delay time inseconds, the polarity of the input, and the triggering behavior must be set. In addition, the outputsettings, Log Event, Capture Waveform, and/or Send e-mail must be entered.