UPS OPERATING INSTRUCTIONSPower Xpert 9395 UPS (450–550 kVA) Installation and Operation Manual 164201701 Rev 3 www.eaton.com/powerquality7-165. Press the SELECT pushbutton on the UPS Command menu bar.The UPS transfers to Energy Saver mode and the critical load is immediatelysupplied by the bypass source. If the bypass source is not available, the powermodule remains on and an alarm sounds.The ONLINE status indicator is illuminated. The UPS status indicates ENERGYSAVER. The Bypass status indicates ON. The UPM status indicates ONLINE. Ifthe battery is not charging, the power module is off.7.3.8 Transfer from Energy Saver to Online ModeTo transfer the critical load to Online mode:NOTE The Energy Saver mode commands are displayed only if enabled at the factory or by an EatonCustomer Service Engineer.1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the UPS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The UPSControl Command screen is displayed.4. On the UPS Control Command screen, select GO TO ONLINE.5. Press the SELECT pushbutton on the UPS Command menu bar.The UPS transfers to Battery mode and then to Online mode. If the powermodule is not available, the system remains on bypass and an alarm sounds.The ONLINE status indicator is illuminated. The UPS status indicates ONLINE. TheUPM status indicates ONLINE.7.3.9 Transfer from Online to High Alert ModeTo transfer the critical load to High Alert mode:NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton CustomerService Engineer.1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the UPS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The UPSControl Command screen is displayed.4. On the UPS Control Command screen, select GO TO HIGH ALERT.